Installing/mounting
3.4 Rack-mounted device
Note
Weatherproof installation
Install the device at a location where it is protected against:
• Direct heat and solar radiation
• Mechanical damage
• Vibrations
• Shock
• Contamination
• Intrusion of dust
• Corrosive media
• Moisture and condensation
• Significant and rapid temperature fluctuations
• Strong air flow
3.4
Rack-mounted device
3.4.1
Safety notes for hazardous areas
Risk of explosion resulting from improper installation
• Install the devices only in control cabinet/enclosure types, in hazardous areas, that meet the
• An air exchange of at least 5-times the volume of the enclosure per hour, but at least 164
32
WARNING
requirements of EN/IEC 60079-7 and are correspondingly approved.
l/h, is required for the introduction of hazardous gases. Ensure the specified air exchange
using suitable ventilation measure.
SIPROCESS GA700 rack and wall mounted devices
Compact Operating Instructions, 06/2023, A5E35134047-AB