Building management system gateway card (modbus)
Hide thumbs Also See for CLIMATE 5000 VRF BMS-MOD:

Advertisement

Parameters Setting:
Parameter
Modbus ID, to distinguish modbus gateway with multiple
Modbus address
Modbus protocols in the same subnet. Don't repeat the address.
Baud rate: suggest 9600
Modbus commu-
Check bit: no checking by default
nication setting
Stop bit: 1StopBit by default
IP address of modbus gateway, multiple IPs can't be the same.
IP address
Default 255.255.255.0
Subnet Mask
Gateway
Local gateway address
Baud rate of the
Outdoor communication baud rate which is connected to modbus gateway
outdoor unit
Click "Application Settings" after changing the corresponding parameters. Click "Get Settings" when apply the new settings. Modbus gateway will
restart automatically after changing settings, the network will break and reconnect.
3.2.
Air Conditioner Information Query
Choose "power winding" or "input register" in the web page to read information of the air conditioner unit.
When choose "power winding" it will be like the picture below.
Fig.3.4
CLIMATE 5000 VRF
Description
Usage Introduction | 7
6720862468 (16/04)