Specifications
Power
9 VAC, 60 Hz, 25 VA transformer minimum
Rechargeable battery: 6.0 VDC, 2.1 Ah NIMH.
Maximum battery charging current is 120 mA.
Once the battery reaches a low battery condition,
a trouble signal will be annunciated, indicating
that the battery may no longer support a full
alarm load.
When fully charged, the battery will operate the
panel without AC power for 24 hours with the
panel in a normal, standby condition, followed by
5 minutes in full alarm condition (including the
maximum specified auxiliary load of 250 mA).
Radio frequency
319.5 MHz
Storage temperature
-29 to 140ºF (-34 to 60ºC) without battery
14 to 86ºF (-10 to 30ºC) with battery one year
shelf life
Operating
32 to 120ºF (0 to 49ºC)
temperature
Maximum humidity
85% relative humidity, noncondensing
Auxiliary power
Unregulated 4.0 to 12.3 VDC, with a maximum of
250 mA
Regulatory information
Some installation may require configurations dictated by
city/state codes, insurance, or Underwriter's Laboratories (UL). This
section describes the various component and configuration
listings.
Basic system:
•
Control panel: Backup battery 6 V 2.1 Ah (34-070)
•
Standard Class 2, 9 VAC, 25 VA power transformer (UTC Fire &
Security part 22-155) or Standard, Class 2, 9 VAC, 30 VA (UTC
Fire & Security part 22-153).
•
Hardwired siren (13-374)
Household burglary alarm system unit (UL 1023), basic system
plus the following:
•
Hardwired magnetic contact (1038T) or wireless learn mode
door/window sensor (60-670-95R or
60-362N-10-319.5 or 60-362N-11-319.5)
•
Panel piezo beeps set to on
•
Entry delay set to 45 seconds or less
•
Exit delay set to 60 seconds or less
•
RF time-out set to 24 hours
•
Control panel alarms turned on
•
Auto arm set to on
•
Siren timeout set to 5 minutes or more
•
Trouble beeps set to on
•
RF jam detect set to on
•
Hardwired siren supervision set to on
•
Exit extension set to off
•
Quick exit set to off
10
Household fire warning system (UL 985), basic system plus the
following:
•
Wireless smoke sensor 60-848-02-95, TX-6010-01-1 learned
into sensor group 26.
•
Panel piezo beeps turned on
•
Control panel alarms set to on
•
Siren timeout set to 4 minutes or more
•
Trouble beeps set to on
•
RF jam detect set to on
•
Hardwired siren supervision set to on
•
Smoke supervision set to on
UL 1635 digital alarm communicator system the following settings
are required only if the system is set up for central station
reporting:
•
Phone mode 1 set to "All SIA" or "All CID"
•
Automatic phone test set to 001
•
RF timeout set to 4 hours
•
AC power failure report set to on
•
CPU low battery report set to on
•
Fail to communicate set to on
•
Entry delay plus the dialer delay must not exceed 60 seconds
SIA system requirements
Verified to SIA CP-01-2007 by ETL, basic system, plus if multiple
annunciations are required, use hardwired siren 13-046.
Note:
For UL 1635 installations, entry delay plus dialer abort delay
must not exceed 60 seconds.
Table 8 below describes programming requirements to meet
ANSI-SIA CP-01.
Table 8: SIA setting requirements
Function
Default setting
Entry delay
30 seconds
Exit delay
60 seconds
Dialer delay
30 seconds
Auto arm
On
Unvacated premises
On
Call waiting
Off
Alarm cancel window
6 minutes
System test
Enabled
Communication test
Enabled
Exit extension
On
Swinger shutdown
On (one trip)
Fire alarm verify
Off
Required setting
30 to 240 seconds
45 to 240 seconds
15 to 45 seconds
On
On
On if reporting to
central station and
customer has call
waiting service
6 to 255 minutes, Off
Enabled
Enabled
On
On (one trip)
On
Simon XTi Installation Guide