Option
Terminal
Code
Symbol
41
FR
Starting Contact Signal
OHF
Heat Sink Overheat
42
Warning
LOC
Low load detection
43
44
MO1
General Output 1
MO2
General Output 2
45
46
MO3
General Output 3
IRDY
Inverter Ready Signal
50
51
FWR
Forward Rotation
52
RVR
Reverse Rotation
53
MJA
Major Failure Signal
54
WCO
Window Comparator for
Analog Voltage Input
55
WCOI
Window Comparator for
Analog Current Input
58
FREF
Frequency Command
Source
59
REF
Run Command Source
SETM
2
60
62
EDM
STO (Safe Torque Off)
Performance Monitor
(Output terminal 11
only)
63
OPO
Option card output
64
GSS
GS synchronization
(Ver.3.2 or
output
after)
255
no
No assignment
Output Function Summary Table
Function Name
nd
Motor Selection
ON
Either FW or RV command is given to the inverter.
OFF
No FW or RV command is given to the inverter, or
both are given to the inverter.
ON
Temperature of the heat sink exceeds a specified
value (C064).
OFF
Temperature of the heat sink does not exceed a
specified value (C064).
ON
Motor current is less than the specified value
(C039).
OFF
Motor current is not less than the specified value
(C039).
ON
General output 1 is ON.
OFF
General output 1 is OFF.
ON
General output 2 is ON.
OFF
General output 2 is OFF.
ON
General output 3 is ON.
OFF
General output 3 is OFF.
ON
Inverter can receive a run command.
OFF
Inverter cannot receive a run command.
ON
Inverter is driving the motor in forward direction.
OFF
Inverter is not driving the motor in forward
direction.
ON
Inverter is driving the motor in reverse direction.
OFF
Inverter is not driving the motor in reverse
direction.
ON
Inverter is tripping with major failure.
OFF
Inverter is normal, or is not tripping with major
failure.
ON
Analog voltage input value is inside of the window
comparator.
OFF
Analog voltage input value is outside of the
window comparator.
ON
Analog current input value is inside of the window
comparator.
OFF
Analog current input value is outside of the
window comparator.
ON
Frequency command is given from the operator.
OFF
Frequency command is not given from the
operator.
ON
Run command is given from the operator.
OFF
Run command is not given from the operator.
nd
ON
2
motor is being selected.
nd
OFF
2
motor is not being selected.
ON
STO is being performed.
OFF
STO is not being performed.
ON
(output terminal for option card).
OFF
(output terminal for option card).
ON
GS1/2 signal is synchronized.
OFF
GS1/2 signal is NOT synchronized.
ON
(input ignored)
OFF
(input ignored)
80
Description