DHW tank Switch box layout
DHW Tank Temp. (15m) CNS042(YEL)
❋ Use a correct sensor pocket which is fit for the DHW tank sensor(OD Ø6).
If the gap between the supplied sensor and DHW tank sensor pocket is big, use thermal grease.
• When you set the hot water supply temperature to 55°C or less, do not use the booster heater.
- The heatpump and the booster heater operate until the initial set temperature is reached. After that, only the
NOTE
booster heater may operate depending on the settings.