Testing/Maintenance - Honeywell NOTIFIER NFS2-640 Manual

Hide thumbs Also See for NOTIFIER NFS2-640:
Table of Contents

Advertisement

12 spaces for extended
custom label
Type Code
Silenceable (Y/N) Device Function
CONTROL
Y
BELL CIRCUIT
Y
STROBE CKT
Y
HORN CIRCUIT
Y
AUDIBLE CKT
Y
SPEAKER
N
REL END BELL
N
blank label
Y
REL CKT ULC
N
RELEASE CKT
N
REL AUDIBLE
Y
REL CODE BELL
Y
INSTANT RELE
N
ALARMS PEND
N
CONTROL NAC
Y
GEN ALARM
N
GEN SUPERVIS
N
GEN TROUBLE
N
GENERAL PEND
N
TROUBLE PEND
N

5 Testing/Maintenance

When finished with the original installation and all modifications, conduct a complete operational test on the entire installation to verify compliance with applicable
NFPA standards. Testing should be conducted by a factory-trained fire alarm technician in the presence of a representative of the Authority Having Jurisdiction and the
owner's representative. Follow procedures outlined in NFPA Standard 72's section on Inspection, Testing and Maintenance. All test and maintenance instruction codes
and software necessary to provide test and inspection requirements of CAN/ULC-S536, Standard for the Inspection and Testing of Fire Alarm Systems.
NOTE: Use 0 (zero) ohm impedance when testing wire-to-wire faults.
Disable or Enable a Point
WARNING: DO NOT USE SOFTWARE FOR RELEASING LOCKOUT
!
DO NOT RELY ON DISABLE/ENABLE SOFTWARE SETTINGS TO LOCK OUT RELEASING DEVICES. RELEASING DEVICES
MUST BE PHYSICALLY DISCONNECTED.
NOTE: When an input or output point associated with releasing functions is disabled, a single supervisory trouble will be generated.
32
Type Code
P R O G R A M C O N T R O L
0 0 _ _ _ _ _ _ _ _ * O W
Default zone
Five zones for CBE list; the default zone
selection is 00 (general alarm)
Switch Inhibit: I=selected; *=off (default)
Silenceable: O=selected; *=off (default)
Supervised NAC
Supervised NAC for notification appliance
Supervised NAC for notification appliance
Supervised NAC for notification appliance
Supervised NAC for notification appliance
Supervised NAC for speaker circuits
Supervised NAC
Supervised NAC for undefined device
Releasing Circuit, power-limited (Class 2), supervised for opens, shorts and ground faults (always non-
silenceable)
Releasing circuit, non-power-limited, supervised for opens and ground faults
NAC, activated upon release
Supervised NAC (NFS2-640 NAC only)
NAC, short = normal; supervised for open circuits and ground faults. Always non-silenceable and switch-
inhibited.
Output that will activate upon receipt of an alarm condition, and remain in the alarm state until all alarms have
been acknowledged. It is programmed as "switch inhibit".
Supervised NAC
Control Module, an XPC-8 circuit, or an XP5-C (in NAC mode) configured as a Municipal Box Transmitter for
NFPA 72-2002 Auxiliary Fire Alarm Systems applications (MBT-1 required). This Type ID can also be used for
general alarm activation. It is programmed as "switch inhibit".
Control Module, an XPR-8 relay, or an XP5-C (in relay mode) activated under any Supervisory condition (includes sprinkler
type). It is programmed as "switch inhibit".
Control Module, an XPR-8 relay, or an XP5-C (in relay mode) activated under any System Trouble condition. It is programmed
as "switch inhibit".
Control Module, an XPC-8 circuit, or an XP5-C (in NAC mode) that will activate upon receipt of an alarm and/or trouble
condition, and remain in the ON state until all events have been ACKNOWLEDGED.
Control Module, an XPC-8 circuit, or an XP5-C (in NAC mode) that will activate upon receipt of a trouble condition, and remain
in the ON state until all troubles have been ACKNOWLEDGED. It is programmed as "switch inhibit".
Table 10 NAC Type Codes
20-character user-editable custom label
N o t i f i c a t i o n D e v N o 1
NFS2-640 UL Listing Document — P/N 52741LD:H9 5/19/2022
B 0 1
The address of a NAC connected
through NAC 1 (B01), NAC 2
(B02), NAC 3 (B03), or NAC 4
(B04)
Walk Test Selection: *=off (default);