Cc-Link Local/Remote Operation - Toshiba CC-Link TOSVERT VF-S11 Option Instruction Manual

Hide thumbs Also See for CC-Link TOSVERT VF-S11:
Table of Contents

Advertisement

6. CC-Link local/Remote Operation

The example below shows how to configure the VF-S11 for local/remote operation.
F terminal.................Operating command
R terminal ................CC-Link local/remote (Terminal in this example) switching
VIA terminal............Operation frequency command
<Wiring>
(Variable resistor: 1 to 10k ohm)
Recommendation value 3k ohm
<Parameter setting>
cmod
fmod
f112
<Operation>
R-CC terminal open: VF-S11 is controlled as a slave device of CC-Link.
R-CC terminal closed: F-CC terminal short to RUN
Variable resistor for adjustment:
Frequency setting
Operation command
CC-Link/local Switch
(Command mode selection)
(Frequency setting mode selection 1) = 1 (VIA)
(Input terminal selection 2 (R))
F-CC terminal short to STOP
Output frequency is set up by the VIA signal input.
- 20 -
1/4W-4.7k ohm
10k ohm
= 0 (Terminal board)
= 48 (Remote/Local control)
E6581422③
VF-S11
P24
VIA
SW2
F
SOURCE
SINK
R
CC

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cc-link ccl002z

Table of Contents