Programming

3.3 Programming
3.3.1 DCC Participation
In a system with both MN and Fire, DCC must always be disabled for all NFS-320/SYSs, NFS2-640s, NFS2-3030s, NCA-2s and
ONYXWorks Workstation.
NFS2-3030/NCA-2
Panel: In the Panel Settings Menu, set DCC Participation to NO
to disable DCC Participation.
VeriFire Tools: Leave the Display and Control Center box unchecked in the NFS2-3030 and NCA-2. Do not enable DCC.
NFS2-3030 General Settings Branch, "General
NFS2-640/NFS-320/SYS
Panel: In the Utility Program Menu, set "DCC-mode" to "N" (no) to
disable DCC participation.
18
Settings 1" column
Figure 3.2 VeriFire Tools, NFS2-3030/NCA-2
P A N E L S E T T I N G S
L C M L O C A L M O D E : Y E S
P O W E R M A N A G E M E N T M O D E : O F F
D C C P A R T I C I P A T I O N : N O
R A P I D A L L C A L L : N O
D E F A U L T S E T T I N G S
Figure 3.1 Panel Settings Screen (2), NFS2-3030
NCA-2 General Settings Branch, "General
Settings 2" column
Leave
unchecked.
R E G I O N = 0
L O C A L C O N T R O L = 0 I P - A C C E S S = 0 D C C - m o d e : N
Figure 3.3 Utility Program, NFS2-640/NFS-320/SYS
Mass Notification — P/N LS10063-000NF-E:E 06/26/2019
Programming
R E G I O N A L S E T T I N G S
M O R E
A C C E P T
B A C K
T B L . R E M I N D = 2
A L A . S C R O L L = N