Connection Limitations - LG MULTI V 5 Engineering Manual

Hide thumbs Also See for MULTI V 5:
Table of Contents

Advertisement

CONNECTION LIMITATIONS

Table 13: Outdoor Unit Connection Limitations.
Outdoor Unit Model No.
208-230V
460V
ARUM072BTE5
ARUM072DTE5
ARUM096BTE5
ARUM096DTE5
ARUM121BTE5
ARUM121DTE5
ARUM144BTE5
ARUM144DTE5
ARUM168BTE5
ARUM168DTE5
ARUM192BTE5
ARUM192DTE5
ARUM216BTE5
ARUM216DTE5
ARUM241BTE5
ARUM241DTE5
ARUM264BTE5
ARUM264DTE5
ARUM288BTE5
ARUM288DTE5
ARUM312BTE5
ARUM312DTE5
ARUM336BTE5
ARUM336DTE5
ARUM360BTE5
ARUM360DTE5
ARUM384BTE5
ARUM384DTE5
ARUM408BTE5
ARUM408DTE5
ARUM432BTE5
ARUM432DTE5
ARUM456BTE5
ARUM456DTE5
ARUM480BTE5
ARUM480DTE5
ARUM504BTE5
ARUM504DTE5
22 | ODU PRODUCT DATA
Nominal Cooling
(Btu/h)
Max. Qty.
72,000
96,000
120,000
144,000
168,000
192,000
216,000
240,000
264,000
288,000
312,000
336,000
360,000
384,000
408,000
432,000
456,000
480,000
504,000
©
Indoor Units
Sum of Indoor Unit Nominal Cooling Capacities (Btu/h)
Min. Capacity (Btu/h)
(50%)*
13
36,000
16
48,000
20
60,000
24
72,000
29
84,000
32
96,000
35
108,000
39
120,000
42
132,000
45
144,000
52
156,000
55
168,000
58
180,000
61
192,000
64
204,000
64
216,000
64
228,000
64
240,000
64
252,000
Max. Capacity (Btu/h)
(130%)
93,600
124,800
156,000
187,200
218,400
249,600
280,800
312,000
343,200
374,400
405,600
436,800
468,000
499,200
530,400
561,600
592,800
624,000
655,200

Hide quick links: