Mitsubishi Electric 800 Series Instruction Manual page 102

Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

4.3.4
Changing the frequency (60 Hz, initial value) at the
maximum voltage input (5 V, initial value)
• Change the maximum frequency.
With a 0 to 5 VDC input frequency setting potentiometer, change the frequency at 5 V from 60 Hz (initial value) to 50 Hz.
Adjust the setting so that the inverter outputs 50 Hz when 5 V is input. Set "50 Hz" in Pr.125.
Operating procedure
1.
Changing the maximum frequency
Set "50.00 Hz" in Pr.125.
2.
Checking the mode/monitor
Press
to change to the monitor / frequency monitor.
3.
Start
Turn ON the start switch (STF or STR), then turn the potentiometer (frequency setting potentiometer) clockwise
slowly to full. (Refer to steps 2 and 3 in 4.3.3.)
Operate at 50 Hz.
NOTE
• To set the frequency at 0 V, use the Pr.902.
Output frequency
• Other adjustment methods for the frequency setting voltage gain are the following: adjustment by applying a voltage
directly across terminals 2 and 5, and adjustment using a specified point without applying a voltage across terminals 2 and
5.
Parameters referred to
Pr.125 Terminal 2 frequency setting gain frequency
Pr.902 Terminal 2 frequency setting bias frequency
Pr.903 Terminal 2 frequency setting gain
Initial value
60 Hz
(Hz)
Bias
Pr.902
0
Frequency setting signal
0
0
Pr.902
page 328
page 328
page 328
Gain
Pr.125 (Pr.903)
100%
5 V
10 V
Pr.903
4.3 Basic operation procedure (External operation)
3
4
5
4
5
6
7
8
9
10
101
4. BASIC OPERATION