Chapter 3 Overview
User settings (continued)
Submenu
Local settings
LCD
(continued)
Audible alarm
In/Out settings
Output voltage
[ The UPS
unit must be
in Standby
Output frequency
Mode in order
to change the
In/Out
settings ]
Output mode
Input volt hysteresis
Bypass transfer
Overload pre-alarm
18
Available settings
Modify LCD screen brightness and
contrast to be adapted to room light
conditions.
[Enabled] [Disabled on battery]
[Always disabled]
Enable or disable the buzzer if an
alarm occurs
[200V] [208V] [220V] [230V] [240V]
[250V]
Can be changed only in Standby mode
Frequency converter:
[Enabled] [Disabled]
Frequency settable in frequency
converter mode
[Industrial] [Network]
Set UPS behaviour regarding transfer
on Bypass
Sets input voltage hysteresis from 1
to 10V
[Transfer if BP AC NOK]
[Enabled] [Disabled]
Allow transfer on Bypass out of
tolerance
[10%] ... [102%]
Load % when overload alarm occurs
6U Rack or Tower UPS RT8kVA and RT11kVA IUOMG
Default settings
[Enabled]
[230V]
[Disabled]
[Network]
[10 V]
[Enabled] for 3:1
(8PX and 9PX)
models
[Disabled] for 1:1
(8KX and 9KX)
models
[102%]