Siemens SIMATIC NET CP 1542-5 Equipment Manual page 44

Table of Contents

Advertisement

Technical specifications
6.4 Ambient temperature
The following derating factors and maximum ambient temperatures apply.
Table 6- 2
Installation altitude
(Height above mean
sea level)
-1000 m to 2000 m
2000 m to 3000 m
3000 m to 4000 m
4000 m to 5000 m
Basic value for applying the derating factor is the maximum permissible ambient temperature in °C
1)
Note
• The derating factors compensate for the decreasing cooling effect of air at higher altitudes
due to lower density.
• Linear interpolation between altitudes is permissible.
44
Restrictions of the maximum permissible ambient temperature in relation to the
installation altitude
Derating factor
for 2000 m.
Maximum ambient temperature when the rack is
1)
1.00
0.93
0.86
0.78
Equipment Manual, 01/2023, C79000-G8976-C326-05
mounted horizontally
60 °C
56 °C
52 °C
47 °C
SIMATIC CP 1542-5

Advertisement

Table of Contents
loading

This manual is also suitable for:

S7-1500

Table of Contents