5.1.3
Assembly of floor standing outdoor unit
A
1
2
Fig. 9
Floor standing outdoor unit
[1] Floor bracket (accessory)
[2] Rubber pads
[A] Screw the floor brackets to the concrete and fix the rubber pads
[B] Place the outdoor unit on the floor brackets
[C] Screw the outdoor unit to the floor brackets
Anchor the unit to a constructive base on concrete platform with a
minimum thickness of 10 cm or galvanized metal construction raised by
10cm.
5.1.4
Installation of the condensation drain
NOTICE
Carry out drainage piping as mentioned in this chapter.
▶ If drainage is not perfect, water leaks may damage the surrounding
area.
Install the drain connector after placing and fixing the outdoor unit.
1. Assemble the washer rubber into the drain connector.
2. Connect a 16mm drain hose to the drain connector, the drain hose
should be installed downwards to allow smooth flow of draining
water.
Compress 3400i AWS – 6721825369 (2021/11)
B
1
Fig. 10 Installation of drain connector
[1]
Rubber washer
[2]
Drain connector
[3]
Drain hose (not supplied with the outdoor unit)
Installation
C
0010036733-001
2
3
0010036819-001
11