Electrical installation
194 HI -त् व रित इं स ् ट ाले श न और स् ट ार् ट -अप गाइड
Refer to
Electrical installation
wiring accordingly. The BIO-01 module has removable spring clamp terminals. Use
ferrules on the multistranded cables before assembly.
■
BIO-01 विद् य ु त कने क ् श न
Sample wiring with the ABB standard macro:
Terminals
External sample connection
EN
HI
Start-up
■
BIO-01 इं स ् ट ॉल करे ं
The BIO-01 module is automatically identified by the drive firmware. To configure the
By default, RIIO-01 module is provided in ACS560 standard R0...R2 drives. You can
inputs refer to the ACS480 firmware manual
remove the RIIO-01 module and can install BIO-01 and/or fieldbus adapter module
(+Fxxx).
BIO-01 /
1.
2.
RIIO-01
RIIO-01 ACS560-01 R0 ... R2
a.
b.
RIIO-01
on page 55. If you configure the inputs, set up the
Aux. voltage output and prog. digital input
+24V Aux. output +24 V DC, max. 200 mA
DGND Aux. voltage output common
DCOM Digital input common for all
DI1
Stop (0)/Start (1)
DI2
Forward (0)/Reverse (1)
Digital and analog I/O extension BIO-01
DI3
Constant frequency/speed selection
DI4
Constant frequency/speed selection
DI5
Ramp set 1 (0)/Ramp set 2 (1)
DO1
Not configured
AI1
Output frequency/speed ref: 0...10 V
+10V Ref. voltage +10 V DC (max. 10 mA)
GND Analog circuit common / DO common
SCR Signal cable shield / DO screen
Safe torque off (STO)
SGND Safe torque off. Factory connection.
Both circuits must be closed for the
IN1
drive to start.
IN2
OUT1
,
,
Description
Base
(3AXD50000047399 [English])
Internal connection
unit
X
X
X
X
X
X
X
X
X
.