DOK-SUPPL*-VAC*01*****-IT04-EN-P
IndraControlVAC 01 Y-Repeater
Connecting two operator displays via the Y-repeater
Resolution in pixels
Cable lengths between the con‐
trol cabinet PC and the operator
display
without Y-repeater
Cable lengths between the con‐
trol cabinet PC and the Y-re‐
peater
Cable lengths between the Y-
repeater and the operator dis‐
play
Total cable length between the
control cabinet PC and the op‐
erator display
with Y-repeater
Tab. 10-2:
Cable lengths permitted for the Y-repeater
Malfunctions if the total cable lengths exceeds 100 m. The total
cable lengths between the control cabinet PC and the operator
display may not exceed 100 m.
If the total cable lengths between the control cabinet PC and the operator dis‐
play exceeds 30 m, the data transmission for USB devices connected to the
operator display is limited. Also refer to the chapter "S1 DIP switch" in the
operating instructions of the relevant operator display.
Control cabinet PC
SXGA: 60 m max.
XGA: 70 m max.
SVGA: 80 m max
Total cable length: 100 m max.
Fig. 10-5:
Maximum cable length between the operator display and the control
cabinet PC
To connect two operator displays to a control cabinet PC, the Y-repeater is
switched between the control cabinet PC and both the operator displays. As
the screen signals are transmitted to both operator displays, data can only be
entered with the active operator display. Which of the two operator displays
can be used as active operator display to operate the control cabinet PC has
to be selected with a 24 V signal, see
inputs" on page
35.
Bosch Rexroth AG
Mounting, demounting and electric installation
SVGA
XGA
SXGA
800 × 600
1024 ×
1920 ×
768
1080
< 80 m
< 70 m
< 60 m
< 80 m
< 70 m
< 60 m
< 80 m
< 70 m
< 60 m
< 100 m
< 100 m
< 100 m
Y-repeater
SXGA: 60 m max.
XGA: 70 m max
SVGA: 80 m max.
chapter 12.1 "Function of the digital
29/53
FHD
WXGA
1280 ×
1366 ×
1024
768
< 50 m
< 70 m
< 50 m
< 70 m
< 50 m
< 70 m
< 100 m
< 100 m
Operator display no. 1
Operator display no. 2