IP Gateway KNX/BACnet N143
Integrated Webserver
The device is equipped with a web server presenting the configuration and current values in an overview page.
This presentation is helpful for testing purposes and for documentation of the interface between KNX and
BACnet.
Note
The web server is disabled in the ETS parameters for security reasons. To use it, it must first be activated by a
corresponding ETS parameter under "Options".
The web page contains a header section showing general device specific information:
 Device name
 Device description
 Installation location
 BACnet instance number of the device
 Firmware version
 Physical KNX address
 IP address
 Netmask
 Gateway address
 MAC address
 Number of configured objects
 Maximum number of possible COV subscriptions
 Current number of COV subscriptions
 Number of binary input objects
 Number of binary output objects
 Number of binary value objects
 Number of analog input objects
 Number of analog output objects
 Number of analog value objects
 Device status
 Revision number
 Priority: This displays the priority array, which is used to transmit events from KNX to BACnet
Siemens Schweiz AG
Smart Infrastructure
Global Headquarters
Theilerstrasse 1a
CH 6300 Zug
A6V10466141 RS-AC
 Siemens AG 2022
Subject to change
GAMMA instabus
Technical Product Information
June 2022
5WG1143-1AB01
http://www.siemens.com/gamma-td
5 / 12