4 Installation and Commissioning
Table 4-1
No.
1.
Connect the individual modules to a suitable
module rack.
2.
Connect the PM 1507 with the power supply
system (230 V alternating current).
3.
Interconnect the following devices:
PROFINET interface of the PG/PC to the PROFINET interface of the S7 CPU
PROFINET interface of the S7-CPU with the PROFINET interface of ET 200SP
Reader cable with the CM 4xIO link (see \9\, Chapter 3.1)
4.2

Installing the software

Note
It is recommended to run the latest versions of any installed software.
TIA Portal with Step 7 and WinCC
Table 4-2
No.
1.
Install STEP 7 Professional V17
2.
Install WinCC Professional V17
3.
Install the PCT Tool V3.4 HF2
4.
Install the IODD file for RF220R with IO-Link
interface
\4\
4.3

Commissioning

4.3.1

Restore S7-1500 CPU factory setting

Before you begin with the commissioning of the application, the S7-1500 CPU must
have the factory settings (see \8\, Chapter 13.5).
Under the following circumstances you can reset the S7-1500 to the original factory
settings:
No memory card has been inserted in the CPU.
The CPU is in STOP mode.
Procedure via the mode switch:
Put the mode switch to MRES position. Keep the mode switch in this position
until the RUN/STOP LED lights up for the second time and remains lit (after
three seconds). Then release the switch again.
Set the mode switch to the MRES position again within the next three seconds
and then back to STOP.
Read/write data with IO-Link
Entry ID: 73565887,
V3.4,
Action
Action
\3\
06/2022
Remarks
When wiring the 24V, make sure that the
polarity is correct.
Remarks
Follow the instructions of the
installation program.