Ceiling panel

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
(5) Installation of adjust corner cap/suction grille
Install the adjust corner cap/suction grille in the reverse procedure of
installation to the indoor unit.
• For this ceiling panel, the direction of the suction grille can be changed on
customer's demand when multiple indoor units are installed.
A. Installation of adjust corner cap
1. Hook the strap of the adjust corner cap surely to the pin of
the ceiling panel.
2. As shown in Fig.7, install the adjust corner cap to the ceiling panel and
fix it by tightening screw at the suction port corner. (Attached accessory)
* Screw tightening torque should be below 12 N•m (1.2 kgf•m).
3. Insert the claws of the adjust corner cap into hole at the ceiling panel
corner and push in the adjust corner cap until you feel quick feeling.
Fix the adjust corner cap by turning screw clockwise at the suction port
corner of the ceiling panel.
(Screw tightening torque should be below 12 N•m (1.2 kgf•m).) (Fig. 7)
• After fixing, if claws at the both sides of the adjust corner cap float
from the ceiling panel, push in the adjust corner cap.
4. When tightening a screw, do not use an electric screwdriver.
B. Installation of suction grille
• To install the suction grille, follow to the reverse procedure of the removal.
This ceiling panel can be installed from anyone of 4 directions by turning
the suction grille. Change the direction on the customer's demand or
according to the direction matching of the suction grille
when multiple units are installed.
• When installing the suction grille, be sure not to pinch
the flap motor wiring connector.
• Be sure to attach a strap to prevent falling of the suction
grille to the ceiling panel.
A. Check after installation
• Check again there is no clearance between the indoor unit and the ceiling panel, and between the ceiling panel
and the ceiling surface.
* A clearance causes water leak or dewing.
• Check the cables are connected surely.
* Incomplete connection causes such a trouble as the flap does not work.
B. For wireless remote controller
• For details of installation, refer to the Installation Manual attached to the
wireless remote controller kit (sold separately).
After confirmation of the above items, hand a set of this manual, manuals for the indoor unit,
manual for products sold separately, etc. to the customer.
For cleaning of the filter, be sure to ask the maintenance professional.
3. Others
4
Pin
(Fig. 7)
Hook hole of
ceiling panel
Hook of
fall-preventive strap
(Fig. 8)
4 direction-free
EH99622701 (ENGLISH)

Advertisement

loading

This manual is also suitable for:

Rbc-um11pgwe