Group Number Setting
u
Group Number setting for Indoor Units
① Confirm the power of whole system(Indoor Unit, Outdoor Unit) is OFF, otherwise turn off.
② The communication lines connected to INTERNET terminal should be connected to central control of
Outdoor unit with care for their polarity( A ' A, B ' B )
③ Turn the whole system on.
④ Set the group and Indoor Unit number with a wired remote control.
⑤ To control several sets of Indoor Units into a group, set the group ID from 0 to F for this purpose.
WARNING
• Valve address and central control address of its corresponding indoor unit should be set identical in
manual addressing.
Outdoor Units
Terminal block on the main PCB
SODU B SODU A
B
A
Group recognizing the simple central controller
No.0 group (00~0F)
No.1 group (10~1F)
No.2 group (20~2F)
No.3 group (30~3F)
No.4 group (40~4F)
No.5 group (50~5F)
No.6 group (60~6F)
No.7 group (70~7F)
No.8 group (80~8F)
No.9 group (90~9F)
No. A group (A0~AF)
No. B group (B0~BF)
No. C group (C0~CF)
No. D group (D0~DF)
No. E group (E0~EF)
No. F group (F0~FF)
EX)
HR unit
IDU
IDU
INT B
INT A
B(D)
A(C)
Valve (04)
Valve (03)
Valve (02)
Valve (01)
Central control address
HR Unit PCB
Indoor unit (04)
Indoor unit (03)
Indoor unit (02)
Indoor unit (01)
Installation Manual 93