● After EPO is triggered, there is no SmartLi output.
● After EPO is triggered, the system reports a Battery cabinet shutdown alarm.
Press the external EPO switch that connects to the dry contact card or remove the
4-pin terminal on the EPO port of the dry contact card of the bypass unit.
4.2.4 Clearing the EPO State
Procedure
Step 1 Clear the EPO state. Ensure that the EPO button connected to the external EPO is
not in the EPO state.
Step 2 On the LCD screen, choose System Status > Alarms > Clear Faults. In the
displayed dialog box, tap Yes. The Battery cabinet shutdown alarm is cleared
successfully.
Figure 4-2 Clear Faults
Step 3 View active alarms and ensure that the Battery cabinet shutdown alarm has
disappeared from the alarm list.
----End
4.3 Commissioning Smart Cooling Products
Prerequisites
The power-on commissioning for the upstream PDF of air cooled precision smart
cooling products is completed.