Proceed as follows:
1.
Connect a three-wire power cord to the ac Power 3-Terminal Block on the first
H201Ti (item 8 in Figure 2-4 on page 2-8): The live side to L1/L, the other side to
L2/N, and the ground to E/G. For additional wiring details, see Table D-1 on
page D-1.
2.
Connect the second end of the two-pair supervisory link cable coming out of the
H201Ti to the main terminal block on the H201Ci-C (item 5 in Figure 3-2 on
page 3-3).
3.
Power On the H201Ti.
4.
Ensure the H201Ti is operating normally and no gas or fail alarms are present, by
looking at the small LED indicators on the right side of the I/O module (refer to
Section 2.4.6.3 on page 2-11).
5.
Repeat the steps 1 to 4 above until all H201Ti's are connected to the H201Ci-C.
6.
Connect a power cord to the ac Supply Connector on the H201Ci-C (item 19 in
Figure 3-3 on page 3-5).
7.
Power On the H201Ci-C.
ELECTRICAL SHOCK HAZARD. Turn off the electric power at the
WARNING
CAUTION
fuse box or service panel before making any electrical connections,
and ensure a proper ground connection is made before connecting
line voltage. Failure to do so can result in property damage, personal
injury and/or death.
8.
Repeat the steps 1 to 7 above until all H201Ci-C's are fed.
7.2.2

Initial Observations

1.
On each Hydran 201Ci-C, verify the Supervisory Link Supply indicator (green,
DS12; item 15 in Figure 3-3 on page 3-5) is lit.
Part 17997
Verification of Operation Prior to Installation
Rev. 6, March 2011
7-3