Special Conditions For The Safe Use Of Intrinsically Safe Positioners; Use, Operation - ABB TZIDC Manual

Digital positioner
Table of Contents

Advertisement

TZIDC DIGITAL POSITIONER | CI/TZIDC/C-FM-US-EN REV. A
Outside of the housing is a connector for the
equipotential bonding.
The following opportunities are available:
Direct connection of single-strand wires of up to
2
2.5 mm
or
Direct connection of fine wires of up to 1.5 mm
Connection of cross-sections of up to 6 mm
ring or spade terminal with 4 mm drill hole.
For proper selection of cables see electrical installation
instructions in the original manufacturer's manual. Use
cables rated at least 20 K greater than the ambient
temperature.
High / recurring charging processes in gas areas must be
excluded by the operator.
Notes for operation
The positioner shall be included in the local equipotential
bonding system
Either only intrinsically or non intrinsically safe circuits shall
be connected. A combination is not permitted.
When the Positioner is operated with non intrinsically safe
circuits, the subsequent use for type of protection Intrinsic
Safety is not permitted.
Special conditions for the safe use of intrinsically safe
positioners
Special conditions
The 'Local communication interface (LCI)' may only be used
outside of the explosion hazardous area with U
Measures of lightning protection have to be provided by the
2
or
user.
2
using a
Special conditions for safe use of Positioners non I.S.
Only devices which are suitable for the operation in explosion
hazardous areas declared as zone 2 and the conditions
available at the place of operation are allowed to be
connected to circuits in the zone 2.
The connecting and disconnecting as well as the switching of
circuits under voltage are only permitted during installation,
for maintenance or repair purposes.
Note
The temporal coincidence of explosion hazardous atmosphere
and installation, maintenance resp. repair purposes is assessed
as improbably.
For the circuit 'Mechanical digital feedback' measures have
to be taken outside the device that the rated voltage is
exceeded not more than 40 % by transient disturbances.
Only non combustible gases are allowed to be used as
pneumatic auxiliary energy.
Only suitable cable entries which meet the requirements of
IEC 60079-15 are allowed to be used.

Use, operation

The TZIDC is only approved for intended and appropriate use. In
case of non-compliance, the warranty and manufacturer's
liability do no longer apply!
In explosive atmospheres only such auxiliary components
shall be used that meet all requirements of the European and
the national standards.
The ambient conditions specified in the instruction manual
have to be adhered to strictly.
The TZIDC has only been approved for its appropriate and
intended use in standard industrial atmospheres. Where
aggressive substances are present in the air, the
manufacturer has to be consulted.
7
≤ 30 V DC.