Chapter 7 Buffer read/write instructions
7.2 Buffer write instructions
7.2.1 PUT / PUTP instructions
FUN(234)
PUT, PUTP
FUN(235)
Instructions
M
n1
PUT
S
¡
PUTP
D
n2
Input
condition
PUT(P)
* Available only when do not use computer link module or data link module
1) Functions
Write the data of 'n2' words, which start at the address specified as 'S' of CPU, and
transfer the data into the block starting at the address specified as 'D' of buffer memory
inside the A/D module mounted at the slot number 'n1'.
Buffer memory
of A/D module
[ D ]
[ D+n2-1 ]
PUT
PUTP
Available devices
P
K
L
F
T
C
¡
¡ ¡*
¡
¡
n1 D S n2
'n2' words
Applicable CPU
S
D
#D Integer
¡
¡
¡
¡
¡
Operand setting
Slot number at which A/D
n1
module is mounted
Start address of buffer memory
D
at which data will be written
Start address of source data of
D
CPU module
n2
Number of word to be written
CPU module
[ S ]
[ S+n2-1 ]
7 - 6
K200S
K300S
K1000S
Flag
Steps
Error
Zero
Carry
(F110)
(F111)
(F112)
¡
9