Summary of Contents for Honeywell ADEMCO LYNX XL Series
Page 1
ADEMCO LYNX XL SERIES ADEMCO LYNX XL SERIES ADEMCO LYNX XL SERIES ADEMCO LYNX XL SERIES Security System Security System Security System Security System LXL- - - - 1010 1010 1010 1010 Installation and Setup Guide Installation and Setup Guide...
Page 2
RECOMMENDATIONS FOR PROPER PROTECTION The Following Recommendations for the Location of Fire and Burglary Detection Devices Help Provide Proper Coverage for the Protected Premises. Recommendations For Smoke And Heat Detectors With regard to the number and placement of smoke/heat detectors, we subscribe to the recommendations contained in the National Fire Protection Association's (NFPA) Standard #72 noted below.
LXL-1010 Installation and Setup Guide Functions • Night Stay and step arming can be set on the keypad • Single-button arming feature (on keypads or keyfobs): Can use dedicated keys to arm the system AWAY or STAY • Up to 8 schedules, to control devices and/or auto-arm/disarm the system •...
Section 1: Features and Installation Highlights Important Installation Highlights (Installer Please Read) • The Installer keypad (6160 or 6139) for programming uses address 16. Before beginning the installation refer to “Section 2, Setup and Mountingand Quick Mode Programming Installer Keypad Functions”” to become familiar with the use of the Installer Keypads keys used to program the control.
Page 8
LXL-1010 Installation and Setup Guide 1–4 www.PDF-Zoo.com firealarmresources.com...
LXL-1010 Installation and Setup Guide 2. Selecting a Installation Site Plug the LXL-1010 control in at the desired location. Select a duplex outlet location where the controls Red RF LED is not lit. The RED RF LED located on the receiver's circuit board should be used as an indicator of strong local radio frequency interference.
Section 2: Quick Start Installation Guide ARMED READY AWAY STAY TEST BYPASS INSTANT CODE CHIME DELETE READY SELECT PANIC QM-011-V0 INDEX # FUNCTION Used at any time to exit the current menu (without saving current input unless * is pressed) and return to the previous menu.
LXL-1010 Installation and Setup Guide SELECT DEAULTSError! Bookmark not defined.. Scroll to the “Select Defaults ” option to change the current default table. You have a choice of four different default tables. The defaults associated with each configuration are shown in the LXL-1010 Installation and Setup Guide Programming Form.
Section 2: Quick Start Installation Guide SEC PHONE. Scroll to the “Sec Phone” option to enter the central station secondary phone number in the system. Valid entries for the entering the secondary phone number are 0–9, # + 11 for ‘∗’, # + 12 for ‘#’, # + 13 for a pause (2 seconds).
LXL-1010 Installation and Setup Guide To Add a Window, Motion, Fire, Glass Break, or Shock Sensor Scroll to Scroll to sensor Scroll to location sensor type "Add Sensors" 5AA 5AA Activate transmitter Press Press Press twice or enter [SELECT] [SELECT] [SELECT]...
Section 2: Quick Start Installation Guide DELETE SENSORS. Scroll to the “Delete Sensor” option to delete sensors in the system. Delete Sensors Scroll to Scroll to Scroll to Delete "DelZn XX" "Delete Sensors" "Delete Zone" "Zone XX" Scroll Press Press Press Press zone number...
Page 16
LXL-1010 Installation and Setup Guide Using the screws and anchors supplied attach the controls mounting plate to the receptacle adapter and the wall as shown in Figure 5. Figure 5 shows a typical mounting installation using the duplex receptacle adapter. REMOVE RECEPTACLE RECEPTACLE...
Section 2: Quick Start Installation Guide 6. Phone Line Connections For incoming phone line and handset wiring refer to Figure 7. The AUX phone jack on the LXL-1010 provides a convenient means of connecting an additional telephone. DETAIL A INCOMING SIDE VIEW PHONE LINE RING...
Page 18
LXL-1010 Installation and Setup Guide 2–10 www.PDF-Zoo.com firealarmresources.com...
S E C T I O N Programming Overview • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Programming You can program the system at any time, even at the installer's premises prior to the actual installation.
LXL-1010 Installation and Setup Guide Keypads Alpha KeypadsError! Bookmark not defined.: Alpha keypads are identified by predefined addresses as follows: This Device Uses Address Reports As Zone Enabled By… 6160/6139 always enabled, all sounds enabled Installer Keypad 5839 keypad 1 data field *190, *191 5839 keypad 2 data field *190, *191...
Section 3: Programming Overview Function KeysError! Bookmark not defined. To assign functions to 5828/5828V Function Keys refer to the 5828/5828V Installation and Setup Guide. To assign functions to 5839 function keys, use *57 Function Key menu mode. To assign emergency key functions (function key option “00”), first program the respective emergency zone number (95 for “A”...
Page 22
LXL-1010 Installation and Setup Guide Zone Type Description Interior Follower through which one must pass upon entry (to and from the keypad). Provides a delayed alarm (using the programmed entry/exit time) if the entry/exit zone is faulted first. Otherwise this zone type gives an instant alarm.
Section 3: Programming Overview Zone Type Description 24 Hour Carbon The internal sounder output will pulse when this zone type is alarmed. Monoxide Always active and cannot be bypassed. Monitor Type 20 Arms the system in Stay mode when the zone is activated. Arm-Stay Pushbutton units send the user number to the central station when (BR only)
LXL-1010 Installation and Setup Guide Data Field ProgrammingError! Bookmark not defined. Procedures Task Procedure A) Press both [ ∗ ] and [#] at the same time within 50 seconds after Entering Programming Mode power is applied to the control, B) After power-up (“Busy Standby D1” display clears), enter [Installer code (4-1-1-2)] + 8 0 0.
S E C T I O N Data Field Programming • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Data Field Programming The following pages list this control’s data fields in numerical order.
Page 26
LXL-1010 Installation and Setup Guide Zone Sounds & Timing ( ∗ ∗ ∗ ∗ 31– ∗ ∗ ∗ ∗ 39) FIELD TITLE and DATA ENTRIES EXPLANATION Single Alarm Sounding Per Zone Note: This field applies to the internal sounder only. (per armed period) UL installations must be 0 (no limit).
Page 27
Section 4: Data Field Programming Dialer Programming ( ∗ ∗ ∗ ∗ 40 – ∗ ∗ ∗ ∗ 50) FIELD TITLE and DATA ENTRIES EXPLANATION To clear entries from field, press ∗40∗. If fewer than 6 digits need to PABX Access Code be entered, exit by pressing [∗], which advances to the next field.
Page 28
LXL-1010 Installation and Setup Guide FIELD TITLE and DATA ENTRIES EXPLANATION Zone Programming Menu Mode Use this menu mode to program zone information. See Zone Programming section for procedures. Function Key Menu Mode Use this menu mode to program 5839 keypad function keys. See Function Key section for procedures.
Page 29
Section 4: Data Field Programming FIELD TITLE and DATA ENTRIES EXPLANATION Low Bat Report Code Sent when a low-battery condition exists in the system’s battery. UL: Required for UL commercial burglar alarm installations and 0 = no report required for residential fire alarm installations. 1-F = see description above *59 Test Report Code Sent periodically to test that the communicator and phone lines are...
Page 30
LXL-1010 Installation and Setup Guide Output and System Setup (*77 - *93) FIELD TITLE and DATA ENTRIES EXPLANATION Enter the start and end month for daylight savings time, if Daylight Saving Time applicable to the region. Start/End Month 0 = Disabled 4 = April 1 = Jan # + 10 = Oct...
Page 31
Section 4: Data Field Programming EXIT Options Select the desired options. The following table summarizes the Program mode lockout options: 0 = standard *98 installer code lockout 1 = lockout [∗] + [#] reentry after *98 exit Exit Reentry By: (reentry via installer code only) Command Entry Installer Power-up†...
Page 32
LXL-1010 Installation and Setup Guide Ring Count For Downloading Refer to the chart below and program this field accordingly. answer down- 0–15 = number of rings before control picks Set field ∗ ∗ ∗ ∗ 95 to… machine loading up phone line. 1-14 (not 0) higher than number of rings set on answer machine (e.g., if ans.
Page 33
Section 4: Data Field Programming Enter the types of reports to be sent to pager 1. *162 Pager 1 Report Options 0 = No reports sent † 1 = Open/close for all users enabled to page † Reports to pager only when arming (close)/disarming (open) from a 4 = All alarms and troubles keypad using a security code;...
Page 34
LXL-1010 Installation and Setup Guide Zone Type 90 Report Codes Enter the desired 3-digit Contact ID® report codes for alarms and *183 troubles occurring on zones assigned to this zone type. 90 ALARM ID: XXX Press [∗] to accept and continue. TROUBLE ID: XXX Important Notice on Report Codes: To avoid confusion at the central station, it is recommended that existing Contact ID®...
Page 35
Section 4: Data Field Programming Configurable Zone Type Charts Configurable zone types 90 and 91 can be programmed via downloader software or from a keypad using data fields*182-*185. Programming Configurable Zone Type options involves making 10 entries in data field *182 for zone type 90 and field *184 for zone type 91, where each entry represents the sum of the values of the various options shown in the tables below.
Page 36
LXL-1010 Installation and Setup Guide Keypad Programming Fields NOTE: Each keypad must be assigned a unique address. Keypads programmed with the same address will give unpredictable results. FIELD TITLE and DATA ENTRIES EXPLANATION INTERNAL SOUNDER OPTIONS Note: Fire alarm sounds are always enabled regardless of option *188 selected.
S E C T I O N Zone Programming ( ✱ ✱ ✱ ✱ 56 and ✱ ✱ ✱ ✱ 58 Menu Modes) • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Zone Programming ✱...
Page 38
LXL-1010 Installation and Setup Guide PROMPT VALID ENTRIES EXPLANATION Each zone must be assigned to a zone type, which defines the way in Zone Type (ZT) 10 Zone Type which the system responds to faults in that zone. 00-24, 90, 91 = zone type (see Perimeter Enter the Zone Type code from the list below: table at right)
Page 39
✱ ✱ Section 6: Zone Programming ( 56 and 58 Menu Modes) PROMPT VALID ENTRIES EXPLANATION This prompt will only appear if you answered “Yes” at the first Confirmation Option XMIT TO CONFIRM prompt in this section. [∗] to continue ✱...
Page 40
LXL-1010 Installation and Setup Guide PROMPT VALID ENTRIES EXPLANATION This display appears upon entry into this mode. Confirm? SET TO CONFIRM? The default is 0 (No). 0 = no 0 = NO 1 = YES 0 1 = yes If 1 (Yes) is entered, you will be prompted to confirm each transmitter [∗] to continue after entering the serial and loop numbers (at the “XMIT TO CONFIRM”...
Page 41
✱ ✱ Section 6: Zone Programming ( 56 and 58 Menu Modes) PROMPT VALID ENTRIES EXPLANATION If the serial/loop number combination transmitted does not match the If Serial or Loop Entd A022-4063 serial and loop number entered, a display similar to the one below Numbers do not match Rcvd A022-4064...
Page 42
LXL-1010 Installation and Setup Guide PROMPT VALID ENTRIES EXPLANATION Confirm 13. If “Yes” was entered at the SET TO CONFIRM? prompt XMIT TO CONFIRM previously (see first prompt following entry into the Q58 Expert [∗] to continue ✱ PRESS TO SKIP Programming Mode), the display on the left will appear.
S E C T I O N Function Key Programming ( ✱ ✱ ✱ ✱ 57 Menu Mode) • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Function Keys About Function Key Programming The system provides the ability to program each of the four 5839 keypad function keys to perform...
Page 44
LXL-1010 Installation and Setup Guide 6–2 www.PDF-Zoo.com firealarmresources.com...
S E C T I O N Output Device Programming ( ✱ ✱ ✱ ✱ 79 and ✱ ✱ ✱ ✱ 80 Menu Mode) • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Device Programming Output Devices: The system supports Powerline Carrier devices (X-10 devices).
Page 46
LXL-1010 Installation and Setup Guide *80 Menu Mode: Defining Output Functions Use this mode to program output function definitions (up to 24 functions) that provide automated control of any of the output devices, based on events occurring on individual zones or zones with certain zone types.
Page 47
✱ ✱ Section 7: Output Device Programming ( 79 and 80 Menu Mode) Activated By Select where the initiating event for this output definition is to occur 01 Activated By: as follows: 0 = delete Zone List 0 = delete (deletes the output function and any previous 1 = zone list programming;-see prompt below) 2 = zone type...
Page 48
LXL-1010 Installation and Setup Guide “C” If zone number was selected, this screen appears. Zone Number 01 Enter Zn No. Enter the desired zone number associated with this output number. Press [ ✱ ] to continue. Enter the zone event that will activate this output. 01 Enter Event 0 = restore;...
S E C T I O N Alpha Descriptor Programming ( ✱ ✱ ✱ ✱ 82 Menu Mode) • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Descriptor Programming The system lets you assign zone descriptors for protection zones, keypad panics, and RF receiver supervision faults.
Page 52
LXL-1010 Installation and Setup Guide First 3-Digit Index No. Press [#] plus the 3-digit number for the first word from the Alpha ✱ Z N 0 1 B A C K see index for entries Vocabulary List. Example: The descriptor that we wish to enter for zone 1 is BACK DOOR.
Page 53
Alpha Descriptor Programming Adding Custom Words You can add up to 10 installer-defined words to the built-in vocabulary, which can then be used when programming zone descriptors. Each of the 10 words can actually consist of a word string of one or more words, but no more than ten characters can be used for each word or word string.
Page 54
LXL-1010 Installation and Setup Guide ALPHA VOCABULARY LIST (For Entering Zone Descriptors) ∗ (Word Space) DOOR LEFT RIGHT WING ∗ DOWN LEVEL ROOM WIRELESS – A – ∗ DOWNSTAIRS LIBRARY ROOF – X – DRAWER LIGHT XMITTER – S – ∗...
S E C T I O N Creating Schedules • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Schedules The system provides up to 8 schedules, which can be used to control 11 types of system events at pre- defined times.
Page 56
LXL-1010 Installation and Setup Guide PROMPT VALID ENTRIES EXPLANATION Repeat Option Enter the desired repeat option for this schedule. R E P E A T O P T I O N e.g., To make a schedule that happens everyday you would select all 0 = do not repeat 0 - 4 days with a repeat count of 1.
S E C T I O N System Communication • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • LXL-1010 and Dialer Communication with Central Station This system accommodates several formats for reporting alarms and other system conditions to the Central Station.
Page 58
LXL-1010 Installation and Setup Guide The following table lists codes for reports sent in different formats: Code for Code for Type of 3+1/4+1 3+1/4+1 Code for Report Standard Expanded Alarm SSS(S) A SSS(S) A SSSS AZ AAA(A) Z Trouble SSS(S) T SSS(S) T SSSS Tt TTT(T) t...
Page 59
Section 12: System Communication GG = 01 (system messages show “00”) ZZZ = Zone/contact ID number reporting the alarm, or user number for open/close reports. System status messages (AC Loss, Walk Test, etc.) contain zeroes in the ZZZ location. TABLE OF CONTACT ID EVENT CODES Code Definition Code...
Page 60
LXL-1010 Installation and Setup Guide 11-4 www.PDF-Zoo.com firealarmresources.com...
LXL-1010 Installation and Setup Guide Refer to the user guide for detailed procedures on adding/deleting security codes and changing user attributes. The following is a brief description of how to add user codes. Adding a User Code: Master code + [8] + 2-digit user no. + user’s code Deleting a User Code: Master code + [8] + 2-digit user no.
Section 12. System Operation Function Description key on the keypads (see “Single-Button Arming” above). Disarming Enter code + OFF [1]. If entry delay or an alarm is active, you do not need to press OFF. Bypassing Zones Enter code + BYPASS [6] + zone number(s). Forced (Quick) Bypass To automatically bypass all faulted zones, use the “Quick Bypass”...
LXL-1010 Installation and Setup Guide Setting the Real-Time Clock Set the time and date by doing the following: Alpha Display: +[#] + [6] [3] (Security Code) DISARMED READY TO ARM 2. Press [∗] when the time/date is displayed. TIME/DATE A cursor appears under the first digit of the hour. 04:04PM 10/17/00 ∗...
Page 65
Section 12. System Operation Various Security System Trouble Displays Alpha Display Fixed Disp. Meaning ALARM CANCELED will appear if an exit or interior zone contained a fault during closing at the time the Exit Delay ended (e.g., exit door left open), but the system was disarmed during the Entry Delay time.
Page 66
LXL-1010 Installation and Setup Guide 12–6 www.PDF-Zoo.com firealarmresources.com...
S E C T I O N Testing LXL-1010 • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Test Procedures After the installation is complete, you should perform the following tests: System Test:...
LXL-1010 Installation and Setup Guide The keypads will display all zone numbers of wireless units programmed into the system. Fault each transmitter in turn, causing each one to send a signal. As the system receives a signal from each of the transmitters, the zone number of that transmitter disappears from the display. 2.
Testing LXL-1010 Frequency of the reports is set in Scheduling mode (event 11) or by the following key commands: installer code + [#] + 0 + 0 = test report sent every 24 hours installer code + [#] + 0 + 1 = test report sent once per week installer code + [#] + 0 + 2 = test report sent every 28 days Each mode sets schedule 08 to the stated repeat option;...
Page 70
LXL-1010 Installation and Setup Guide 13-4 www.PDF-Zoo.com firealarmresources.com...
S E C T I O N Specifications & Accessories • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • SECURITY CONTROL 1.
Page 72
LXL-1010 Installation and Setup Guide 5800 Series Transmitter Input Loop Identification All of the transmitters illustrated below have one or more unique factory assigned input (loop) ID codes. Each of the input loops requires its own programming zone (e.g., a 5804's four inputs require four programming zones). LOOP 3 LOOP 2 NOTE: For information on any transmitter...
Page 73
Section 14. Specifications & Accessories Compatible 5800 Series Transmitters Table (continued) Model Product Input Type Description Heat Detector One-piece rate-of-rise heat detector with a built-in transmitter. 5809 • Two reed switches 5815 Door/Window • Transmits supervisory, tamper and low battery messages Transmitters Has two unique input (loop) codes: one for a wired closed circuit 5816...
Page 74
LXL-1010 Installation and Setup Guide 14–4 www.PDF-Zoo.com firealarmresources.com...
Page 75
LIMITED WARRANTY Honeywell International Inc., acting through its Security & Custom Electronics business ("Seller") 165 Eileen Way, Syosset, New York 11791, warrants its product(s) to be in conformance with its own plans and specifications and to be free from defects in materials and workmanship under normal use and service for 24 months from the date stamp control on the product(s) or, for product(s) not having a manufacturer’s date stamp, for 12 months from date of...