[2-9 Example System with an MA and an ME Remote Controller ]

2-9

Example System with an MA and an ME Remote Controller

2-9-1
System with a Connection of System Controller to Centralized Control
Transmission Line
(1) Sample control wiring
Move the male connector
from CN41 to CN40.
SW5-1 OFF ON
Leave the male
connector on
CN41 as it is.
SW5-1 OFF ON
(2) Cautions
1)
Be sure to connect a system controller.
2)
ME remote controller and MA remote controller cannot both be con-
nected to the same group of indoor units.
3)
Assign to the indoor units connected to the MA remote controller ad-
dresses that are smaller than those of the indoor units that are con-
nected to the ME remote controller.
4)
No more than 2 ME remote controllers can be connected to a group
of indoor units.
5)
No more than 2 MA remote controllers can be connected to a group
of indoor units.
6)
Do not connect the terminal blocks (TB5) on the indoor units that are
connected to different outdoor units with each other.
7)
Replace the power jumper connector of the control board from CN41
to CN40 on only one of the outdoor units.
8)
Provide an electrical path to ground for the S terminal on the terminal
block for centralized control on only one of the outdoor units.
9)
When the number of the connected indoor units is as shown in the
right table, one or more transmission boosters (sold separately) are
required.
To connect two transmission boosters, connect them in parallel.
(Observe the maximum number of connectable indoor units that are
26
- chapter 2
Group
OC
HB
51
52
TB3
TB3
M1M2
M1M2
S
TB7
M1M2
S
To be connected
Group
OC
HB
53
54
TB3
TB3
S
M1 M2
M1 M2
TB7
To be left
M1 M2
S
unconnected
Note1
System controller
*1 When only the LM adapter is connected, leave SW5-1 to OFF (as it is).
A B S
*2 LM adapters require the power supply capacity of single-phase AC 220 - 240V.
L12
IC
IC
01
02
TB5
TB15
TB5
TB15
M1M2
S
1 2
M1M2
S
1 2
A1 B2
MA
L22
Group
IC
IC
03
04
TB5
TB5
TB15
TB15
M1M2
M1M2
S
1 2
S
1 2
A1 B2
A1 B2
104
MA
RC
listed in the specifications for each outdoor unit.)
When the W/WP/WL200 and
W/WP/WL250 models are not includ-
ed in the connected indoor units
When the W/WP/WL200 and
W/WP/WL250 models are included in
the connected indoor units
The above table shows the number of transmission
boosters that is required by the system with four HBCs.
For each HBC added or subtracted, subtract or add two
indoor units.
Refer to the DATABOOK for further information about
how many booster units are required for a given system.
10) When a power supply unit is connected to the transmis-
sion line for centralized control, leave the power jumper
connector on CN41 as it is (factory setting).
Group
IC
06
TB5
TB15
M1M2
S
1 2
A1 B2
106
RC
IC
05
TB5
TB15
M1M2
S
1 2
Number of transmission booster
(sold separately) required
1 unit
2 units
13 - 32
33 - 50
units
units
9 - 24
25 - 40
units
units
3 units
-
41 - 50
units
BS_02_L