5
Installing a Water-Cooled Module
Installation Requirements
5.1
Installation Requirements
Checking for Air Pressure at Needle Valves
5.2
Installing a Water-Cooled Module
5.3
Installation environment: enclosed indoor environment in which the temperature and humidity
can be controlled within the ranges of 4°C to 45°C and 5% RH to 90% RH respectively. If the
indoor installation position is ventilated, it should be more than 5 km away from the sea or
pollution sources (such as salt lakes, chemical plants, mineral plants, thermal power plants, and
coal mines).
Horizontal Installation on Concrete Bases
Unit: mm
Needle valve on the refrigerant side
13
Needle valve on the cooling
water side
Stacking Scenario
A maximum of four layers of water-
cooled modules can be stacked. If four
layers are stacked, the minimum height
of the installation space is 3 m.
Use the bolts in the fitting bag to secure
the module at the mounting holes (4
PCS).