      7-4.Limit set 
            Limit set can be done 2 different upper limits (alarm) in the range of 4〜20mA(signal  
level 0〜100%) 
            In case signal change gets severe however, chattering might rise often.  
In such case you may be recommended to use integral function or delay function at/from  
higher position (Customers expertise) respectively. 
【Limit 1,2 and action chart of trouble alarm】 
Limit output(upper limit alarm)
Trouble alarm 
                          Power OFF to close COM-NO 
20mA 
4mA 
COM-NO  open 
LED Off 
Power OFF to open COM-NO 
Fig.13. Operation chart(upper limit alarm) 
Device normal 
COM-NO  open 
LED off 
Fig.14. Operation chart(Trouble alarm) 
COM-NO  close 
LED On 
Trouble 
COM-NO  close 
LED on 
- 10 -
Limit set value(ON) 
Limit set value(OFF) 
Time 
COM-NO  open 
LED Off 
Device normal 
COM-NO  open 
LED off 