Table 8: SCADA operation settings
Name
Range/choice
SCADA protocol type
Automatically clear
fault flags
Automatically clear
fault flags time-out
Always allow trip
Table 9: Protocol point configuration
Range/
Name
choice
Line current deadband
1-100
Digital point mapping
and class assignment
Analog point mapping
and class assignment
SCADA operation settings
Unit
Serial DNP3
Yes
No
0-3,600
s
True
False
Protocol point configuration
Unit
0.1 A
Default mapping is protocol database index =
DNP3 index with all points assigned to class 1
Default mapping is protocol database index =
DNP3 index with all points assigned to class 2
Default
Serial
Select this option for serial DNP3.
DNP3
There are several fault flags in the database (e.g., DPID 20, 21, 22 which
indicate a cleared fault has occurred on the line). These flags can be
cleared by the SCADA system operator with a reset control (CPID 8) and/
or after a time-out. This setting determines if the fault flags will be
Yes
cleared after a time-out:
Yes, flags will be cleared by time-out.
No, flags will not be cleared by time-out.
120
See above.
When this setting is false, SCADA controls to Fusesaver are rejected if the
RCU remote control switch is off or a Fusesaver external lever is down.
This setting allows a modification of this behavior so that SCADA trip
controls can always be sent to Fusesavers.
True: The RCU will issue the trip command to the Fusesaver to trip
regardless of RCU remote control switch position and regardless of
Fusesaver external lever position. The Fusesaver will trip regardless of
policy file setting for manual inhibit (see Fusesaver operating
False
instructions IC1000-F320-A170-XX-XXXX).
False: If the RCU Remote Control switch is off or if the external lever
of the Fusesaver is down, then the RCU will reject the trip command
from the SCADA system.
Note: This setting only modifies the handling of SCADA Fusesaver trip
commands.
Default
20
Description/comment
Description/comment
This setting defines an amount by which the line
current changes an event will be created and sent
through the protocol to the SCADA control center.
The mapping and class assignment can be
configured using the RCU Connect utility.
The mapping and class assignment can be
configured using the RCU Connect utility.
13