Philips Bodine BSL20LV-DF Installation Instructions
Philips Bodine BSL20LV-DF Installation Instructions

Philips Bodine BSL20LV-DF Installation Instructions

Advertisement

Quick Links

BSL20LV-DF
Installation Instructions
CLASS 2 OUTPUT
EMERGENCY LED DRIVER
! IMPORTANT SAFEGUARDS !
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
1. To prevent high voltage from being present on yellow & yellow/black output leads prior to installation,
converter connector must be open. Do not join converter connector until installation is complete and AC
power is supplied to the emergency driver. Do not join converter connector until installation is complete and
AC power is supplied to the emergency driver.
2. This product is for use with an emergency LED lighting load and supplies 20.0 W of power with a maximum
rated current of 1.1 A with a maximum voltage of 50 VDC in emergency mode for a minimum of 90 minutes.
3. Make sure all connections are in accordance with the National Electrical Code or Canadian Electrical Code and
any local regulations.
4. To reduce the risk of electric shock, disconnect both normal and emergency power supplies and converter
connector of the emergency driver before servicing.
5. This emergency driver is suitable for both factory or field installation. For field installation, please see the
instructions on page 2.
6. This product is suitable for use in damp locations where the ambient temperature is 0ºC minimum, +50ºC
maximum. Product is not suitable for heated air outlets and wet or hazardous locations. Maximum allowable
case temp is 65ºC. See Product Unit Label for measurement location.
7. An unswitched AC power source is required (120-277 VAC, 50/60 Hz).
8. Do not install near gas or electric heaters.
9. Do not attempt to service the battery. A sealed, no-maintenance battery is used that is not field replaceable.
Contact the manufacturer for information on service.
10. The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
11. Do not use this product for other than intended use.
12. Servicing should be performed by qualified service personnel.
13. Equipment should be mounted in locations and at heights where it will not be subjected to tampering by
unauthorized personnel.
14. For Canadian application the output terminals should be in compliance with the accessibility requirement of
the Canadian Electric Code.
15. This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions:(1)
this device may not cause harmful interference, and (2) this device must accept any indifference that may
cause undesired operation.
THIS PRODUCT CONTAINS A RECHARGEABLE NICKEL-CADMIUM BATTERY.
236 Mt. Pleasant Rd. • Collierville, TN USA 38017-2752 • Tech Support 888-263-4638 • Fax 901-853-5009 • www.philips.com/bodine
SAVE THESE INSTRUCTIONS
THE BATTERY MUST BE RECYCLED OR DISPOSED OF PROPERLY.
© Philips Emergency Lighting
WHEN USING ELECTRICAL EQUIPMENT, BASIC
SAFETY PRECAUTIONS SHOULD ALWAYS BE
FOLLOWED, INCLUDING THE FOLLOWING:
Ni - Cd
01/31/17
70100294
CONFORMS TO
UL STD 924
CERTIFIED
TO CSA STD
C22.2 NO.141

Advertisement

loading

Summary of Contents for Philips Bodine BSL20LV-DF

  • Page 1 THIS PRODUCT CONTAINS A RECHARGEABLE NICKEL-CADMIUM BATTERY. THE BATTERY MUST BE RECYCLED OR DISPOSED OF PROPERLY. 01/31/17 © Philips Emergency Lighting 236 Mt. Pleasant Rd. • Collierville, TN USA 38017-2752 • Tech Support 888-263-4638 • Fax 901-853-5009 • www.philips.com/bodine 70100294...
  • Page 2 INSTALLATION CAUTION: DO NOT JOIN CONVERTER CONNECTOR UNTIL INSTALLATION IS COMPLETE AND AC POWER IS SUPPLIED TO THE EMERGENCY DRIVER. NOTE: Make sure the necessary branch circuit wiring is available. An unswitched source of power is required. The emergency driver must be fed from the same branch circuit as the AC driver. This product is suitable for field installation with suitable LED loads including LED luminaires, DC voltage driven LED replacements for fluorescent lamps and others.
  • Page 3 Fixture or STEP #2a INSTALLING THE 2W-ITS ON FIXTURE SURFACE Test/Monitor Plate > Mount the supplied 2W-ITS (2 wire illuminated test switch) in a location that is 2 Wire Illuminated visible and accessible by maintenance personnel. The 2W-ITS mounts through a Test Switch Hex Nut ½”...
  • Page 4 OPERATION During normal operation AC power is applied, the charging indicator light is illuminated, indicating that the battery is being charged. When power fails, the emergency LED driver automatically switches to emergency power (internal battery), operating the LED load for a minimum of 90 minutes. When AC power is restored, the emergency driver returns to the charging mode.