LG MULTI V WATER MINI Engineering Manual page 61

Table of Contents

Advertisement

The following is an example of manual pipe size calculations. Designers are highly encouraged to use LATS instead of manual calculations.
Water Mini System Using Y-branches and Header
Example: Five (5) indoor units connected
Water Source Units (WSU).
IDU: Indoor Units.
Y-branches.
Header.
A: Main Pipe from First Y-branch.
B: Pipe from Y-branch to Y-branch or Header.
C: Pipe from Y-branch or Header to Indoor Unit.
D: Pipe to Farthest Indoor Unit.
• Indoor units must be installed at a lower position
than the Header.
• Y-branch pipes cannot be used after Headers.
• Install the Header so that the pipe distances
between the between the connected indoor
units are minimized. Large differences in pipe
distances can cause indoor unit performances
to fluctuate.
• Always reference the LATS software report.
Table 29: Pipe Capabilities.
Length
A + ΣB + ΣC + D ≤475.7 feet
Elevation1
Elevation2
Distance between fittings and indoor units
Distance between fittings and
Y-branches
Distance between two Y-branches
Distance between Header and indoor units
For calculation purposes, assume equivalent pipe length of Y-branch is 1.6 feet, and equivalent pipe length of header is 3.3 feet.
1
Table 30: Refrigerant Pipe Diameter (B) from Y-branch to Y-branch / Header.
Downstream Total Capacity of Indoor Units (Btu/h)
≤19,100
< 54,600
≤76,400
• Connection piping from branch to branch cannot exceed the main pipe diameter (A) used by the water source unit.
• Y-branches and other header branches cannot be installed downstream of the initial header branch.
REFRIGERANT PIPING DESIGN
First Y-branch
Total pipe length
Elevation differential (Water source unit ↔ Indoor unit)
Elevation differential (Indoor unit ↔ Indoor unit)
Liquid Pipe (Inches O.D.)
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
Water Source Unit
To Water
Source
Unit
B
C
IDU
C
Second Y-branch
IDU
Longest actual pipe length
A + B + D ≤230 feet
Longest pipe length after first branch
B + D ≤ 131 feet
≤ 98.4 feet
≤ 49 feet
Vapor Pipe (Inches O.D.)
Ø1/4
Ø3/8
Ø3/8
Y-branch
To Indoor
Units
Header
C
IDU
IDU
Length: ≤230 feet
: ≤131 feet
D
Longest Equivalent pipe length
A + B + D ≤295.2 feet
≥20 inches
≥20 inches
≥20 inches
≥20 inches
Ø1/2
Ø5/8
Ø3/4
LIMITS / PL ACEMENT | 61
Pipe Sizing
Brazed Cap
C
IDU
1