Connecting Water Pipes - Huawei FusionCol8000-E400 Quick Manual

Hide thumbs Also See for FusionCol8000-E400:
Table of Contents

Advertisement

Method 2: Installing a Ground Cable
Ground cables can be
routed through plastic-
coated metal hoses for
protection based on site
requirements.
4

Connecting Water Pipes

1. The water pipes are connected using thread connectors. The threaded joints must be sealed
with sealing tape or thread adhesive.
2. Clean the external water pipes before connecting them to the water inlet and outlet pipes.
3. Connect the water inlet and outlet pipes of the FusionCol8000-E using thread connectors.
When connecting the water pipes, do not exert excessive force to prevent damage to the
pipes. (When connecting the pipes, use two pipe wrenches or chain pliers.)
4. At low temperatures, take thermal insulation measures to prevent water pipes from
freezing.
5. Water pipes must be wrapped with thermal insulation foam (including the buried pipes).
1. Install water pipes.
When installing the water seal,
keep it horizontal and allow a
maximum downward inclination of
5°.
Install the water seal in strict
accordance with the figure to avoid
reverse connection.
(1) Condensate drainpipe (DN25)
(2) Spray drainpipe (DN40)
(3) Spray water refill pipe (DN20)
6