Electric Characteristics - LG MULTI V ARNU07GTUA4 Engineering Product Data Book

Hide thumbs Also See for MULTI V ARNU07GTUA4:
Table of Contents

Advertisement

Indoor unit

8. Electric Characteristics

Model
ARNU07GBGA4
ARNU09GBGA4
ARNU12GBGA4
ARNU15GBGA4
ARNU18GBRA4
ARNU24GBRA4
ARNU28GBRA4
ARNU36GB8A4
ARNU42GB8A4
ARNU48GB8A4
ARNU07GBGA4
ARNU09GBGA4
ARNU12GBGA4
ARNU15GBGA4
ARNU18GBRA4
ARNU24GBRA4
ARNU28GBRA4
ARNU36GB8A4
ARNU42GB8A4
ARNU48GB8A4
Symbols:
MCA : Min, Circuit Amps(A)
MFA : Max. Fuse Amps(see note 5)
kW : Fan Motor Rated Output(kW)
FLA : Full Load Amps(A)
IFM : Indoor Fan Motor
26 _
Ceiling Concealed Duct (High Sensible)
Unit
Type
Hz
Volts
BG
BG
BG
BG
BR
50
220-240
BR
BR
B8
B8
B8
BG
BG
BG
BG
BR
60
220
BR
BR
B8
B8
B8
Note :
1. Voltage range
Units are suitable for use on electrical systems where voltage
supplied to unit terminals is not below or above the listed range
limits,
2. Maximum allowable voltage unbalance between phases is 2%
3. MCA/MFA
MCA=1.25 x FLA
MFA≤ 4 x FLA
(Next lower standard fuse rating. Min. 15A)
4. Select wire size based on the MCA
5. Instead of fuse, use Circuit Breaker.
Power Supply
Voltage
MCA
MFA
Range
3.31
15
3.31
15
3.31
15
3.31
15
4.40
15
Max:264
Min:198
4.40
15
4.40
15
6.50
15
6.50
15
6.50
15
3.31
15
3.31
15
3.31
15
3.31
15
4.40
15
Max:242
Min:198
4.40
15
4.40
15
6.50
15
6.50
15
6.50
15
IFM
Input(W)
kW
FLA
cooling
0.35
2.65
450
0.35
2.65
450
0.35
2.65
450
0.35
2.65
450
0.37
3.50
450
0.37
3.50
450
0.37
3.50
450
0.75
5.20
800
0.75
5.20
800
0.75
5.20
800
0.35
2.65
450
0.35
2.65
450
0.35
2.65
450
0.35
2.65
450
0.37
3.50
450
0.37
3.50
450
0.37
3.50
450
0.75
5.20
800
0.75
5.20
800
0.75
5.20
800
Heating
450
450
450
450
450
450
450
800
800
800
450
450
450
450
450
450
450
800
800
800