1. Safety Precautions Read the following “SAFETY PRECAUTIONS” carefully before perform any servicing. Electrical work must be installed or serviced by a licensed electrician. Be sure to use the correct rating of the power plug and main circuit for the model installed. ...
Page 4
WARNING Install at a strong and firm location which is able to withstand weight of the set. If the strength is not enough or installation is not properly done, the set will drop and cause injury. For electrical work, follow the wiring rules AS/NZS 3000, national regulation, legistration and this installation instructions. An independent circuit and single outlet must be used.
Page 5
CAUTION Installation or servicing work: It may need two people to carry out the installation or servicing work. Pb free solder has a higher melting point than standard solder; typically the melting point is 50°F – 70°F (30°C – 40°C) higher. Please use a high temperature solder iron.
2. Precaution for Using R32 Refrigerant The basic installation work procedures are the same as conventional refrigerant (R410A, R22) models. However, pay careful attention to the following points: WARNING Since the working pressure is higher than that of refrigerant R22 models, some of the piping and installation and service tools are special.
Page 7
CAUTION 2-5. No ignition sources No person carrying out work in relation to a refrigeration system which involves exposing any pipe work that contains or has contained flammable refrigerant shall use any sources of ignition in such a manner that it may lead to the risk of fire or explosion. He/She must not be smoking when carrying out such work.
Page 8
CAUTION Leak detection methods Electronic leak detectors shall be used to detect flammable refrigerants, but the sensitivity may not be adequate, or may need re- calibration. (Detection equipment shall be calibrated in a refrigerant-free area.) Ensure that the detector is not a potential source of ignition and is suitable for the refrigerant used. ...
Page 9
CAUTION Labelling Equipment shall be labelled stating that it has been de-commissioned and emptied of refrigerant. The label shall be dated and signed. Ensure that there are labels on the equipment stating the equipment contains flammable refrigerant. Recovery ...
3. Specification Model CS-RZ25TKR Indoor POS (EAN) 5025232871346 Model CU-RZ25TKR Outdoor POS (EAN) 5025232871537 Performance Test Condition Phase, Hz Single, 50 Power Supply Min. Mid. Max. Min. Mid. Max. 0.85 2.50 3.00 0.85 2.50 3.00 Capacity BTU/h 2900 8530 10200...
Page 11
Model CS-RZ25TKR Indoor POS (EAN) 5025232871346 Model CU-RZ25TKR Outdoor POS (EAN) 5025232871537 Type Cross-flow Fan Material ASG20K1 Motor Type DC (8-poles) Input Power 47.3 Output Power Cool Heat Cool Heat Cool 1020 Speed Heat 1100 Cool 1280 Heat 1350 Cool...
Page 12
Model CS-RZ25TKR Indoor POS (EAN) 5025232871346 Model CU-RZ25TKR Outdoor POS (EAN) 5025232871537 Height (ID / OD) mm (inch) 290 (11.7/16) / 542 (21-11/32) Unit Width (ID / OD) mm (inch) 799 (31-15/32) / 780 (30-23/32) Depth (ID / OD) mm (inch)
Page 13
Model CS-RZ35TKR Indoor POS (EAN) 5025232871353 Model CU-RZ35TKR Outdoor POS (EAN) 5025232871544 Performance Test Condition Phase, Hz Single, 50 Power Supply Min. Mid. Max. Min. Mid. Max. 0.85 3.50 3.90 0.85 3.50 3.90 Capacity BTU/h 2900 11900 13300 2900 11900 13300 Kcal/h 3010...
Page 14
Model CS-RZ35TKR Indoor POS (EAN) 5025232871353 Model CU-RZ35TKR Outdoor POS (EAN) 5025232871544 Type Cross-flow Fan Material ASG20K1 Motor Type DC (8-poles) Input Power 47.3 Output Power Cool Heat Cool Heat 1010 Cool 1050 Speed Heat 1190 Cool 1310 Heat 1380 Cool 1360 Heat...
Page 15
Model CS-RZ35TKR Indoor POS (EAN) 5025232871353 Model CU-RZ35TKR Outdoor POS (EAN) 5025232871544 Height (ID / OD) mm (inch) 290 (11.7/16) / 542 (21-11/32) Unit Width (ID / OD) mm (inch) 799 (31-15/32) / 780 (30-23/32) Depth (ID / OD) mm (inch) 197 (7-25/32) / 289 (11-13/32) Dimension Height (ID / OD)
Page 16
Model CS-RZ50TKR Indoor POS (EAN) 5025232871360 Model CU-RZ50TKR Outdoor POS (EAN) 5025232871551 Performance Test Condition Phase, Hz Single, 50 Power Supply Min. Mid. Max. Min. Mid. Max. 0.98 5.00 5.60 0.98 5.00 5.60 Capacity BTU/h 3340 17100 19100 3340 17100 19100 Kcal/h 4300...
Page 17
Model CS-RZ50TKR Indoor POS (EAN) 5025232871360 Model CU-RZ50TKR Outdoor POS (EAN) 5025232871551 Type Cross-flow Fan Material ASG33 Motor Type DC (8-poles) Input Power 89.9 Output Power Cool Heat Cool Heat Cool 1000 Speed Heat Cool 1130 Heat 1150 Cool 1180 Heat 1200 Type...
Page 18
Model CS-RZ50TKR Indoor POS (EAN) 5025232871360 Model CU-RZ50TKR Outdoor POS (EAN) 5025232871551 Height (ID / OD) mm (inch) 302 (11-29/32) / 619 (24-3/8) Unit Width (ID / OD) mm (inch) 1102 (43-13/32) / 824 (32-15/32) Depth (ID / OD) mm (inch) 244 (9-5/8) / 299 (11-25/32) Dimension Height (ID / OD)
Page 19
Model CS-RZ60TKR Indoor POS (EAN) 5025232871377 Model CU-RZ60TKR Outdoor POS (EAN) 5025232871568 Performance Test Condition Phase, Hz Single, 50 Power Supply Min. Mid. Max. Min. Mid. Max. 0.98 6.00 6.60 0.98 6.00 6.60 Capacity BTU/h 3340 20500 22500 3340 20500 22500 Kcal/h 5160...
Page 20
Model CS-RZ60TKR Indoor POS (EAN) 5025232871377 Model CU-RZ60TKR Outdoor POS (EAN) 5025232871568 Type Cross-flow Fan Material ASG33 Motor Type DC (8-poles) Input Power 89.9 Output Power Cool Heat Cool Heat Cool 1070 Speed Heat 1090 Cool 1220 Heat 1220 Cool 1270 Heat 1270...
Page 21
Model CS-RZ60TKR Indoor POS (EAN) 5025232871377 Model CU-RZ60TKR Outdoor POS (EAN) 5025232871568 Height (ID / OD) mm (inch) 302 (11-29/32) / 619 (24-3/8) Unit Width (ID / OD) mm (inch) 1102 (43-13/32) / 824 (32-15/32) Depth (ID / OD) mm (inch) 244 (9-5/8) / 299 (11-25/32) Dimension Height (ID / OD)
Page 22
Model CS-RZ71TKR Indoor POS (EAN) 5025232871384 Model CU-RZ71TKR Outdoor POS (EAN) 5025232871575 Performance Test Condition Phase, Hz Single, 50 Power Supply Min. Mid. Max. Min. Mid. Max. 1.70 7.10 8.10 1.70 7.10 8.10 Capacity BTU/h 5800 24200 27600 5800 24200 27600 Kcal/h 1460...
Page 23
Model CS-RZ71TKR Indoor POS (EAN) 5025232871384 Model CU-RZ71TKR Outdoor POS (EAN) 5025232871575 Type Cross-flow Fan Material ASG33 Motor Type DC (8-poles) Input Power 105.0 Output Power Cool Heat Cool Heat Cool 1120 Speed Heat 1160 Cool 1300 Heat 1350 Cool 1400 Heat 1400...
Page 24
Model CS-RZ71TKR Indoor POS (EAN) 5025232871384 Model CU-RZ71TKR Outdoor POS (EAN) 5025232871575 Height (ID / OD) mm (inch) 302 (11-29/32) / 695 (27-3/8) Unit Width (ID / OD) mm (inch) 1102 (43-13/32) / 875 (34-15/32) Depth (ID / OD) mm (inch) 244 (9-5/8) / 320 (12-5/8) Dimension Height (ID / OD)
Page 25
Model CS-RZ80TKR Indoor POS (EAN) 5025232871391 Model CU-RZ80TKR Outdoor POS (EAN) 5025232871582 Performance Test Condition Phase, Hz Single, 50 Power Supply Min. Mid. Max. Min. Mid. Max. 2.30 8.00 9.00 2.30 8.00 9.00 Capacity BTU/h 7840 27300 30700 7840 27300 30700 Kcal/h 1980...
Page 26
Model CS-RZ80TKR Indoor POS (EAN) 5025232871391 Model CU-RZ80TKR Outdoor POS (EAN) 5025232871582 Type Cross-flow Fan Material ASG33 Motor Type DC (8-poles) Input Power 105.0 Output Power Cool Heat Cool Heat 1050 Cool 1160 Speed Heat 1220 Cool 1350 Heat 1400 Cool 1450 Heat...
Page 27
Model CS-RZ80TKR Indoor POS (EAN) 5025232871391 Model CU-RZ80TKR Outdoor POS (EAN) 5025232871582 Height (ID / OD) mm (inch) 302 (11-29/32) / 795 (31-5/16) Unit Width (ID / OD) mm (inch) 1102 (43-13/32) / 875 (34-15/32) Depth (ID / OD) mm (inch) 244 (9-5/8) / 320 (12-5/8) Dimension Height (ID / OD)
4. Features Inverter Technology Wider output power range Energy saving Quick Cooling Quick Heating More precise temperature control Environment Protection Non-ozone depletion substances refrigerant (R32) Long Installation Piping Long piping up to 20 meters (RZ25/35TK) and 30 meters (RZ50/60/71/80TK) during single split connection only ...
5. Location of Controls and Components Indoor Unit Anti-bacterial filter Aluminium fin Front panel Auto OFF/ON button Use when remote control is misplaced Horizontal airflow or a malfunction occurs. direction louver Indicator Manually adjustable. POWER Vertical airflow TIMER direction louver Sunlight Sensor Do not adjust i AUTO-X...
6. Dimensions Indoor Unit 6.1.1 CS-RZ25TKR CS-RZ35TKR <Top View> <Side View> <Front View> <Side View> Air intake direction Air outlet Left piping direction Right piping hole <Bottom View> hole <Remote Control> 92.8 <Rear View> 41-61 <Remote Control Holder> Gas side Liquid side Relative position between the indoor unit and the installation plate <Front View>...
Page 32
6.1.2 CS-RZ50TKR CS-RZ60TKR CS-RZ71TKR CS-RZ80TKR <Top View> <Side View> <Front View> <Side View> Air intake 1102 direction Air outlet Left piping Right piping direction hole <Bottom View> hole <Remote Control> <Rear View> 41-61 <Remote Control Holder> Gas side 63.5 Liquid side Relative position between the indoor unit and the installation plate <Front View>...
Outdoor Unit 6.2.1 CU-RZ25TKR CU-RZ35TKR <Top View> Space necessary for installation 67.6 104.7 104.9 60.5 100 mm 100 mm 1000 mm Anchor Bolt Pitch 320 x 570 2-way valve at Liquid side <Side View> (High Pressure) <Side View> <Front View> 3-way valve at Gas side (Low Pressure)
Page 34
6.2.3 CU-RZ71TKR <Top View> Space necessary for installation (131) 34.7 100 mm 100 mm 1000 mm Anchor Bolt Pitch 360.5 × 613 2-way valve at Liquid side (High Pressure) 3-way valve at Gas side (Low Pressure) <Front View> <Side View> <Side View>...
Page 35
6.2.4 CU-RZ80TKR <Top View> Space necessary for installation 27.5 100mm 100mm 1000mm Anchor Bolt Pitch 360.5 × 613 <Side View> <Side View> <Front View> 3-way valve at Gas side (Low Pressure) 2-way valve at Liquid side Unit : mm (High Pressure) <Chassis>...
Outdoor Unit 9.2.1 CU-RZ25TKR CU-RZ35TKR YELLOW (YEL) OR T(W) REMARKS BLU : BLUE BLK : BLACK SINGLE PHASE POWER SUPPLY TO INDOOR UNIT WHT : WHITE RED : RED BLUE YLW : YELLOW (RED) (BLU) GRY : GRAY OR R(U) OR S(V) GRN : GREEN TERMINAL...
Page 44
9.2.2 CU-RZ50TKR CU-RZ60TKR CU-RZ71TKR YELLOW (YEL) OR T(W) REMARKS BLU : BLUE BLK : BLACK SINGLE PHASE POWER SUPPLY TO INDOOR UNIT WHT : WHITE RED : RED BLUE YLW : YELLOW (RED) (BLU) GRY : GRAY OR R(U) OR S(V) GRN : GREEN TERMINAL TRADEMARK...
Page 45
9.2.3 CU-RZ80TKR REACTOR YELLOW (YLW) TO INDOOR UNIT SINGLE PHASE POWER SUPPLY REMARKS : BLUE : BROWN BLUE TERMINAL TERMINAL : ORANGE : BLACK (BLU) (RED) BOARD BOARD : YELLOW : WHITE CONNECTOR (TRADEMARK) : GRAY : RED WHITE YLW/GRN COMP.
10.2 Outdoor Unit 10.2.1 CU-RZ25TKR CU-RZ35TKR REACTOR SINGLE PHASE POWER SUPPLY TO INDOOR UNIT RAT2 RAT1 (GRY) (GRY) 15.8k TERMINAL BOARD 220u DATA OUTDOOR AIR TEMP. SENSOR (THERMISTOR) (RED) COMMUNICATION t° CIRCUIT FUSE 2 FUSE 3 CN–TH1 t° FUSE 103 (WHT) AC-BLK PIPING TEM P.
Page 49
10.2.2 CU-RZ50TKR CU-RZ60TKR CU-RZ71TKR REACTOR RAT1 RAT2 (GRY) (GRY) 15.8k 220u SINGLE PHASE POWER SUPPLY TO INDOOR UNIT OUTDOOR AIR TEMP. SENSOR (THERMISTOR) t° TERMINAL CN–TH1 t° BOARD (WHT) PIPING TEM P. SENSOR (THERMISTOR) DATA t° (RED) COMPRESSOR TEM P. SENSOR (THERMISTOR) COMMUNICATION CN–TANK CIRCUIT...
Page 50
10.2.3 CU-RZ80TKR REACTOR TO INDOOR UNI T SINGLE PHASE POWER SUPP LY TERMINA L TERMINA L CONNEC TOR BOARD BOARD WHITE YLW/GRN L2-I L2-0 ACN1 ACL1 COM3 ELECTRONIC CONTROLLER (GRAY) (BLACK) (WHITE) (BLACK) (RED) CN-COM CN-COM (MAIN) (YELLOW) (YELLOW) FUSE3 R425 R159 R426...
12. Installation Instruction 12.1 Select the Best Location 12.1.3 Indoor/Outdoor Unit Installation Diagram 12.1.1 Indoor Unit Do not install the unit in excessive oil fume area Piping direction Attention not to bend WARNING up drain hose (Front side) such as kitchen, workshop and etc. Flare connection Right only at outside of...
12.2 Indoor Unit 12.2.1 How to Fix Installation Plate The mounting wall shall be strong and solid enough to prevent it from vibration. Ceiling Wall Wall More than 1 More than 1 More Indoor unit 2 screw than 2 Installation plate 1 222 mm 184 mm PIPE...
Page 59
12.2.2 To Drill a Hole in the Wall and Install a Sleeve of Piping Insert the piping sleeve to the hole. Wall Fix the bushing to the sleeve. Indoor Outdoor Cut the sleeve until it extrudes about 15 mm from the wall. 15 mm Approx.
Page 60
12.2.3 Indoor Unit Installation ● Do not turn over the unit without it’s shock absorber during pull out the piping. It may cause intake grille damage. ● Use shock absorber during pull out the piping to protect the intake grille from damage. Piping Piping Shock absorber...
Page 61
Replace the drain hose Rear view for left piping installation Connection cable Drain hose Piping More than 950 mm Connection cable Drain hose (1.0 ~ 1.5HP) or Drain cap More than 1150 mm Adjust the piping slightly Drain hose (2.0 ~ 3.0HP) downwards.
Page 62
12.2.4.1 Wire Stripping and Connecting Requirement Use complete wire without joining. Wire stripping WARNING Use approved socket and plug RISK OF FIRE with earth pin. JOINING OF WIRES No loose strand when inserted MAY CAUSE Wire connection OVERHEATING in this area must Indoor/outdoor connection AND FIRE.
12.3 Outdoor Unit 12.3.1 Install the Outdoor Unit After selecting the best location, start installation to Indoor/Outdoor Unit Installation Diagram. Fix the unit on concrete or rigid frame firmly and horizontally by bolt nut (ø10 mm). When installing at roof, please consider strong wind and earthquake. Please fasten the installation stand firmly with bolt or nails.
Page 64
12.3.3 Evacuation of the Equipment WHEN INSTALLING AN AIR CONDITIONER, BE SURE TO EVACUATE THE AIR INSIDE THE INDOOR UNIT AND PIPES in the following procedure. Do not purge the air with refrigerants but use a vacuum pump to vacuum the installation. There is no extra refrigerant in the outdoor unit for air purging.
Page 65
12.3.4 Connect the Cable to the Outdoor Unit Remove the control board cover from the unit by loosening the screw. Applicable for :CU-RZ25***, CU-RZ35***, Cable connection to the power supply through CU-RZ50***, CU-RZ60***, CU-RZ71*** Isolating Devices (Disconnecting means). Connect approved type polychloroprene sheathed power supply cord 3 x 1.5 mm (1.0 ~ 1.5HP), 3 x 2.5 mm...
Page 66
For wire stripping and connection requirement, refer to instruction 12.2.4.1 of indoor unit. Note: Isolating Devices (Disconnecting means) should have minimum 3.0 mm contact gap. Earth wire shall be Yellow/Green (Y/G) in colour and longer than other AC wires for safety reason. Always ensure all above connections compliant with national wire rules.
Page 67
12.3.8 Check the Drainage Open front panel and remove air filters. (Drainage checking can be carried out without removing the front grille.) Pour a glass of water into the drain tray-styrofoam. Ensure that water flows out from drain hose of the indoor unit. Drain tray-styrofoam...
12.4 Wired Remote Controller Installation Manual 12.4.1 Safety Precautions Read the following “SAFETY PRECAUTIONS” carefully before installation. Electrical work must be installed by a licensed electrician. The caution items stated here must be followed because these important contents are related to safety. The meaning of each indication used is as below.
Page 69
12.4.2 Attached Accessories Name Diagram Remark Remote controller Remote controller cable Length (9.9 m) Screw Installing the remote controller to an outlet box (M4 machine pitched – 30 mm) (embedded cable) Screw Installing the remote controller to the wall (M4 self tapping – 14 mm) (exposed cable) Remote controller cable holder Holder for remote controller cable at control board...
Page 70
Embed an outlet box (JIS C 8336) into the wall. Outlet box may be purchased separately. Medium-sized square outlet box (obtain locally) Part No. DS3744 (Panasonic Co., Ltd.) or equivalent. Secure the remote controller lower case to the outlet box with the two accessory screws 3. Make sure that the lower case is flat against the wall at this time, with no bending.
Page 71
B. If Remote Controller Cable is Exposed Install the remote controller lower case to the wall with the two accessory screws 4. Fasten the screws properly until screw head is lower than the rib and reach the base of remote controller lower case to ensure they do not damage the PCB inside the remote controller 1.
Page 72
12.4.5 Connecting the Remote Controller Cable to Indoor Unit CAUTION Be sure to turn off the main power before installing and connecting the remote controller. Otherwise, it will cause the electrical shock. Open front grille complete Install back terminal board cover complete. Be (Please refer HOW TO TAKE OUT FRONT careful not to clamp the cable between GRILLE).
13. Installation and Servicing Air Conditioner using R32 13.1 About R32 Refrigerant For air conditioning refrigerants such as R410A, the refrigerants were collected back in order to prevent their air dissipation, to curbe the global warming impact, in case they were released into the atmosphere. In the “4th Environmental Basic Plan”, 80% reduction of greenhouse gas emissions by 2050 is required, and due to this requirement, further reduction in the emission of high greenhouse effect gas, such as CFCs, is required.
Page 74
2. Characteristic of Pressure As shown in Table 2, R32 does not have much difference in vapor pressure at the same refrigerant temperature comparing to R410A, but comparing to R22, it is higher at 1.6 times more. Thus, the same as in case of R410A, it is necessary to do installation and service using high-pressure tools and components.
13.3 Refrigerant piping installation • Tools used in services 13.3.1 Required Tools R32 refrigerant air conditioners use the common parts as R410A air conditioners for two-way valves and three-way valves (diameters of service ports); thus, they maintain commonality in the maintenance of the compressive strength, the size of pipe flaring, and the size of flare nuts as R410A.
Page 76
3. Torque wrenches (diameters 1/2, 5/8) Manifold gauges / Charging hoses In order to strengthen the compressive strength, the diameters of wrenches change depending on the flare nut sizes. Torque wrenches Differences in charging hoses Differences in torque wrenches (common R410A) Normal 5.1 MPa 3.4 MPa...
Page 77
7. HFC refrigerant_Electric gas leakage tester 9. Refrigerant cylinders R32 refrigerant is often used for other mixed Refrigerant cylinders for R410A are painted in pink, refrigerant (R410A, R404A, R407C etc.). Therefore, and the ones for R32 are painted in other colors that the usage of existing HFC detectors is possible, but in might subject to change according to the international order to detect more accurately, we recommend to...
Page 78
11. Tools used for refrigerant piping installations and services Tools for R410A Common with R32 Possibility of usage for R22 ○ ○ Pipe cutters, reamers or scrapers ○ ○ Flare tools (clutch type) ○ ○ Torque wrench (1/4, 3/8) ○ ×...
13.4 New installation, Relocation, Repairing of Refrigerant Cycle System The Procedures Relocation Repairing refrigerant cycle Installation Indoor / outdoor units and piping Pump down Refrigerant recovery • Displacing pipes and wires, and displacing indoor / outdoor units Prevention of impurity •...
13.5 Piping installation of R32 13.5.1 Pipe materials used and flaring Copper pipes are used for refrigerant piping. Pipes Pipe thickness which comply with JIS Regulations need to be used. Room air conditioners which use R410A and R32 O and OL materials Thickness (mm) have higher pressure;...
13.6 Installation, Relocation, and Service 13.6.1 Air purge and gas leak test for new installation (using new refrigerant pipes) using vacuum pump (From the point of view of global environment protection, do not release CFCs into the atmosphere during installation work) 1.
Page 82
13.6.2 Process of refrigerant recovery 1. Connect the center charging hose of manifold gauge to the in-let side of recovery device. 2. Connect the valves of the discharge side of recovery device and liquid side of refrigerant cylinder with red hose (charging hose).
Page 83
13.6.3 Relocation 1. Removing the air conditioning unit a) Recovery of outdoor unit refrigerant by pumping down Press “forced cooling button” (as a general rule, since 1998 the name of cooling testing button is changed, and this name is unified within the air conditioning industry), and then you are able to start cooling operation in which the room temperature is low, and you can recover the refrigerant from the outdoor unit.
Page 84
13.6.6 Re-insertion of refrigerant in service When re-insertion is needed, follow the procedures to ensure the insertion of new refrigerant at correct amount. 1. Attach charging hose (blue) to the service port of the outdoor unit. 2. Attach charging hose (red) to the vacuum pump. Fully open the 2-way and 3-way valves. 3.
13.7 Repairing of refrigerant cycle / Brazing point 13.7.1 Preparation for repairing of refrigerant cycle / brazing Brazing which is a technique needed for repairing refrigerant cycle requires advanced technique and experience, and this brazing procedure can only be performed by the workers who completed “Gas Welding Skill Training” regulated by the Occupational Safety and Health Act, and went through the training programs of refrigerant operations.
Page 86
2. Cylinder without adjustment valve side gauge pressure is adjusted by the adjuster. Check the both side valves of the torch and open the cylinder valve to check the remaining refrigerant in the cylinder. Caution: Do not attach oil component on the connection port of the adjuster. Especially, use an oxygen cylinder adjuster which is no oil substance type.
Page 87
13.7.5 Types of flame Types of flame change based on the proportion of propane and oxygen. [Neutral Flame] Perform brazing with this flame (This is a flame when oxygen and propane are mixed at proper proportion, and has lesser effect on the brazed metals) White core flame 10 ~ 15 mm...
Page 88
13.7.7 Selection of brazing material Use BAg brazing material (silver solder) to increase the welding performance. Tensile strength Composition of ingredients (%) Temperature (°C) Characteristics (Reference) Category Standard Brazing Base Number Solidus Liquidus Kgf•cm applications temp material Liquidity is good at low temperature, 49.0 14.5...
Page 89
13.7.10 Checking of brazing (insert) points 1. No impurity on the brazing point Gap 0.025 ~ 0.05 mm If dirt or oil is attached on the brazing point, the brazing filler metal does not reach to junction, and Inner diameter ø6.45 it may cause poor welding.
Page 90
(Reference) Melting temperature of copper • • • • • • • Approx. 1083°C Maximum temperature obtained in propane and oxygen • • • • • • • Approx. 1083°C The important point is to heat the bonding part uniformly within a short period of time until reaching to the brazing temperature in the following manner.
13.8 <Reference> Analysis method for no error code, no cooling / no warming 13.8.1 Preparation for appropriate diagnosis In order to obtain appropriate operation characteristics, minimum 15 minutes or more operation time [testing operation (rated operation)] is required. 1. Method of rated operation (rated operation) For the models which have two buttons of “emergency operation and forced cooling operation”, press forced cooling button once.
Page 92
1. Measuring temperature 1) Indoor unit suction temperature, release temperature, temperature difference, → Measure by thermometer 2) 2-way valve pipe temperature in cooling mode is low temperature (benchmark:5 ~ 10°C), in heating mode is medium temperature (benchmark:25 ~ 35°C). 3) 3-way valve pipe temperature in cooling mode is low temperature (benchmark:7 ~ 15°C) in heating mode is high temperature (benchmark:38 ~ 50°C).
14. Operation and Control 14.1 Basic Function Inverter control, which equipped with a microcomputer in determining the most suitable operating mode as time passes, automatically adjusts output power for maximum comfort always. In order to achieve the suitable operating mode, the microcomputer maintains the set temperature by measuring the temperature of the environment and performing temperature shifting.
Page 94
14.1.5 Automatic Operation This mode can be set using remote control and the operation is decided by remote control setting temperature, remote control operation mode and indoor intake air temperature. During operation mode judgment, indoor fan motor (with speed of Lo-) is running for 30 seconds to detect the indoor intake air temperature.
14.2 Indoor Fan Motor Operation 14.2.1 Basic Rotation Speed (rpm) A. Basic Rotation Speed (rpm) i. Manual Fan Speed [Cooling, Dry, Fan] Fan motor’s number of rotation is determined according to remote control setting. Remote control ○ ○ ○ ○...
14.3 Outdoor Fan Motor Operation Outdoor fan motor is operated with one fan speed only. It starts when compressor starts operation and it stops 30 seconds after compressor stops operation. Compressor: Fan Speed Outdoor Fan: 30 sec 14.4 Airflow Direction ...
Page 97
2. Manual vertical airflow direction can be set using remote control; the angles of the vane are as stated above and the positions of the vane are as Figure 2 below. When the air conditioner is stopped using remote control, the vane will shift to close position.
14.4.3 Horizontal Airflow (RZ50/60/71/80TK) Automatic horizontal airflow direction can be set using remote control; the vane swings left and right within the angles as stated below. For heating mode operation, the angle of the vane depends on the indoor heat exchanger temperature as Figure 1 below.
14.6 Quiet Operation (Heating) Purpose To provide quiet heating operation compare to normal operation. Control condition Quiet operation start condition When “QUIET” button at remote control is pressed. Quiet operation stop condition When one of the following conditions is satisfied, quiet operation stops: ...
14.9 Auto Restart Control When the power supply is cut off during the operation of air conditioner, the compressor will re-operate within three to four minutes (there are 10 patterns between 2 minutes 58 seconds and 3 minutes 52 seconds to be selected randomly) after power supply resumes.
Example of wiring: Core HAJEM-A 240 mm Indoor Unit (XH type) Max 1900 mm #A K1KA04AA0347 (Maker: JST; Maker code: B4B-XHTV4) #B Maker: JST; Maker code: XHP-4 Note: The wire length from indoor unit to the external interface must be within 1.9 meters. The wire must be double insulation type and a ferrite core to be added to reduce noise.
15. Protection Control 15.1 Protection Control for All Operations 15.1.1 Restart Control (Time Delay Safety Control) The Compressor will not turn on within 3 minutes from the moment operation stops, although the unit is turned on again by pressing OFF/ON button at remote control within this period. ...
Page 103
15.1.4 Compressor Overheating Prevention Control Instructed frequency for compressor operation will be regulated by compressor discharge temperature. The changes of frequency are as below. If compressor discharge temperature exceeds 103°C, compressor will be stopped, occurs 4 times per 20 minutes, timer LED will be blinking.
15.2 Protection Control for Cooling & Soft Dry Operation 15.2.1 Outdoor Air Temperature Control The compressor operating frequency is regulated in accordance to the outdoor air temperature as shown in the diagram below. This control will begin 1 minute after the compressor starts. ...
15.2.6 Odor Cut Control To reduce the odor released from the unit. Start Condition AUTO FAN Speed is selected during COOL or DRY operation. During freeze prevention control and timer preliminary operation, this control is not applicable. Control content ...
Page 106
15.3.3 Overload Protection Control The compressor operating frequency is regulated in accordance to indoor heat exchanger temperature as shown below. If the heat exchanger temperature exceeds 60°C, compressor will stop. 60°C Frequency Reduce 55°C 52°C Frequency Limited 49°C 46°C Free Indoor Heat...
16. Servicing Mode 16.1 Auto OFF/ON Button Auto OFF/ON Auto OFF/ON Auto OFF/ON Button pressed Button pressed Button pressed 5 sec 5 sec Auto Operation Test Run Operation Stop Test Run Operation Stop (Forced Cooling Operation) (Forced Heating Operation) Beep Beep x 2 AUTO OPERATION MODE The Auto operation will be activated immediately once the Auto OFF/ON button is pressed.
REMOTE CONTROL RECEIVING SOUND OFF/ON MODE The Remote Control Receiving Sound OFF/ON Mode will be activated if the Auto OFF/ON button is pressed continuously for more than 16 seconds (4 “beep” sounds will occur at 16th seconds to identify the Remote Control Receiving Sound Off/On Mode is in standby condition) and press “AC Reset”...
Page 109
16.2.6 Special Setting mode LCD display area: Special setting display area (highlighted in color) Function Options (If any) Cannot enter this special setting mode under the following conditions: 1 Operation ON. 2 Under [Real/ON/OFF] time setting mode. To enter zone 1 area: Normal display Enter Zone1 mode...
Page 110
Function & Options list: Note: The functions described in the table may not be applicable to the model and may subject to change without further notice. Function Options Remark Name Remote control number selection A, B, C, D Solar radiation sensitivity level adjustment 1, 2, 3, 4, 5 [iAUTO-X/iAUTO/iCOMF, Cool &...
17. Troubleshooting Guide 17.1 Refrigeration Cycle System In order to diagnose malfunctions, make sure that there are no Normal Pressure and Outlet Air Temperature (Standard) electrical problems before inspecting the refrigeration cycle. Gas pressure Outlet air temperature Such problems include insufficient insulation, problem with the (kg/cm (°C) power source, malfunction of a compressor and a fan.
Page 112
17.1.1 Relationship Between the Condition of the Air Conditioner and Pressure and Electric Current Cooling Mode Heating Mode Condition of the Electric current Electric current air conditioner Low Pressure High Pressure Low Pressure High Pressure during operation during operation Insufficient refrigerant ...
17.2 Breakdown Self Diagnosis Function 17.2.1 Self Diagnosis Function (Three Digits Alphanumeric Code) Every press of the button (up or down) will Once abnormality has occurred during operation, increase abnormality numbers and transmit the unit will stop its operation, and Timer LED abnormality code signal to the main unit.
17.3 Error Code Table Diagnosis Abnormality / Abnormality Protection Problem Check location display Protection control Judgment Operation No memory of failure — Normal operation — — Indoor fan only Indoor/outdoor wire terminal Indoor/outdoor operation can Indoor/outdoor After operation for ...
Page 115
Diagnosis Abnormality / Abnormality Protection Problem Check location display Protection control Judgment Operation Check indoor/outdoor Wrong wiring and connection wire and connection Abnormal wiring or — — connecting pipe, expansion pipe piping connection valve abnormality Expansion valve and lead wire and connector ...
17.4 Self-diagnosis Method 17.4.1 H11 (Indoor/Outdoor Abnormal Communication) Malfunction Decision Conditions During startup and operation of cooling and heating, the data received from outdoor unit in indoor unit signal transmission is checked whether it is normal. Malfunction Caused Faulty indoor unit PCB.
Page 117
17.4.2 H12 (Indoor/Outdoor Capacity Rank Mismatched) Malfunction Decision Conditions During startup, error code appears when different types of indoor and outdoor units are interconnected. Malfunction Caused Wrong models interconnected. Wrong indoor unit or outdoor unit PCBs mounted. ...
Page 118
17.4.3 H14 (Indoor Intake Air Temperature Sensor Abnormality) Malfunction Decision Conditions During startup and operation of cooling and heating, the temperatures detected by the indoor intake air temperature sensor are used to determine sensor errors. Malfunction Caused Faulty connector connection. ...
Page 119
17.4.4 H15 (Compressor Temperature Sensor Abnormality) Malfunction Decision Conditions During startup and operation of cooling and heating, the temperatures detected by the outdoor compressor temperature sensor are used to determine sensor errors. Malfunction Caused Faulty connector connection. Faulty sensor.
Page 120
17.4.5 H16 (Outdoor Current Transformer) Malfunction Decision Conditions An input current, detected by Current Transformer CT, is below threshold value when the compressor is operating at certain frequency value for 3 minutes. Malfunction Caused Lack of gas. Broken CT (current transformer).
Page 121
17.4.6 H19 (Indoor Fan Motor – DC Motor Mechanism Locked) Malfunction Decision Conditions The rotation speed detected by the Hall IC during fan motor operation is used to determine abnormal fan motor (feedback of rotation > 2550 rpm or < 50 rpm). Malfunction Caused ...
Page 122
17.4.7 H23 (Indoor Pipe Temperature Sensor 1 Abnormality) Malfunction Decision Conditions During startup and operation of cooling and heating, the temperatures detected by the indoor heat exchanger temperature sensor 1 are used to determine sensor errors. Malfunction Caused Faulty connector connection.
Page 123
17.4.8 H24 (Indoor Pipe Temperature Sensor 2 Abnormality) Malfunction Decision Conditions During startup and operation of cooling and heating, the temperatures detected by the indoor heat exchanger temperature sensor 2 are used to determine sensor errors. Malfunction Caused Faulty connector connection.
Page 124
17.4.9 H25 (nanoe-G Air Purifying System Abnormal) Malfunction Decision Conditions During standby of cooling and heating operation, nanoe-G breakdown occurs and air conditioner stops operation. Malfunction Caused Faulty indoor main PCB. Faulty indoor nanoe-G power module. Troubleshooting When abnormality indication starts again For safety reason and to prevent component breakdown, always switch off the power...
Page 125
17.4.10 H27 (Outdoor Air Temperature Sensor Abnormality) Malfunction Decision Conditions During startup and operation of cooling and heating, the temperatures detected by the outdoor air temperature sensor are used to determine sensor errors. Malfunction Caused Faulty connector connection. ...
Page 126
17.4.11 H28 (Outdoor Pipe Temperature Sensor Abnormality) Malfunction Decision Conditions During startup and operation of cooling and heating, the temperatures detected by the outdoor pipe temperature sensor are used to determine sensor errors. Malfunction Caused Faulty connector connection. ...
Page 127
17.4.12 H30 (Compressor Discharge Temperature Sensor Abnormality) Malfunction Decision Conditions During startup and operation of cooling and heating, the temperatures detected by the outdoor discharge pipe temperature sensor are used to determine sensor errors. Malfunction Caused Faulty connector connection. ...
Page 128
17.4.13 H33 (Unspecified Voltage between Indoor and Outdoor) Malfunction Decision Conditions The supply power is detected for its requirement by the indoor/outdoor transmission. Malfunction Caused Wrong models interconnected. Wrong indoor unit and outdoor unit PCBs used. Indoor unit or outdoor unit PCB defective.
Page 129
17.4.14 H59 (Human Activity Sensor Abnormality) Malfunction Decision Conditions Feedback signal of human activity sensor. Malfunction Caused Feedback signal is fixed at 0 VDC or 5 VDC continuously for 25 seconds during ECONAVI or AUTO COMFORT operation. Feedback signal is detected during ECONAVI or AUTO COMFORT off.
Page 130
17.4.15 H70 (Light Sensor Abnormality) Malfunction Decision Conditions Feedback signal of light sensor. Malfunction Caused Feedback value is 0 VDC continuously. Troubleshooting When abnormality indication starts again. For safety reason and to prevent Check the connector connection: component breakdown, always switch Turn off the power.
Page 131
17.4.16 H97 (Outdoor Fan Motor – DC Motor Mechanism Locked) 17.4.16.1 CU-Z20/25/35/42/50/60/71TKR Malfunction Decision Conditions The rotation speed detected by the Hall IC during fan motor operation is used to determine abnormal fan motor. Malfunction Caused Operation stops due to short circuit inside the fan motor winding. ...
Page 132
17.4.16.2 CU-RZ80TKR Malfunction Decision Conditions The rotation speed detected by the Hall IC during fan motor operation is used to determine abnormal fan motor. Malfunction Caused Operation stops due to short circuit inside the fan motor winding. Operation stops due to breaking of wire inside the fan motor.
Page 133
17.4.17 H98 (Error Code Stored in Memory and no alarm is triggered / no TIMER LED flashing) Malfunction Decision Conditions Indoor high pressure is detected when indoor heat exchanger is detecting very high temperature when the unit is operating in heating operation. ...
Page 134
17.4.18 H99 (Indoor Freeze Prevention Protection: Cooling or Soft Dry) Error Code will not display (no Timer LED blinking) but store in EEPROM Malfunction Decision Conditions Freeze prevention control takes place (when indoor pipe temperature is lower than 2°C). Malfunction Caused ...
Page 135
17.4.19 F11 (4-way Valve Switching Failure) Malfunction Decision Conditions When indoor heat exchanger is cold during heating (except deice) or when indoor heat exchanger is hot during cooling and compressor operating, the 4-way valve is detected as malfunction. Malfunction Caused ...
Page 136
17.4.20 F90 (Power Factor Correction Protection) Malfunction Decision Conditions To maintain DC voltage level supply to power transistor. To detect high DC voltage level after rectification. Malfunction Caused During startup and operation of cooling and heating, when Power Factor Correction (PFC) protection circuitry at the outdoor unit main PCB senses abnormal DC voltage level for power transistors.
Page 137
17.4.21 F91 (Refrigeration Cycle Abnormality) Malfunction Decision Conditions The input current is low while the compressor is running at higher than the setting frequency. Malfunction Caused Lack of gas. 3-way valve close. Troubleshooting When F91 indication happens. For safety reason and to prevent component breakdown, always switch off the power before remove and...
Page 138
17.4.22 F93 (Compressor Rotation Failure) Malfunction Decision Conditions A compressor rotation failure is detected by checking the compressor running condition through the position detection circuit. Malfunction Caused Compressor terminal disconnect. Faulty Outdoor PCB. Faulty compressor. Troubleshooting When F93 indication happens.
Page 139
17.4.23 F95 (Outdoor High Pressure Protection: Cooling or Soft Dry) Malfunction Decision Conditions During operation of cooling or soft dry, when outdoor unit heat exchanger high temperature data is detected by the outdoor unit heat exchanger thermistor. Malfunction Caused ...
Page 140
17.4.24 F96 (IPM Overheating) Malfunction Decision Conditions During operating of cooling and heating, when IPM temperature data (120°C) is detected by the IPM temperature sensor. Multi Models only Compressor Overheating: During operation of cooling and heating, when the compressor OL is activated. Heat Sink Overheating: During operation of cooling and heating, when heat sink temperature data (90°C) is detected by the heat sink temperature sensor.
Page 141
17.4.25 F97 (Compress Overheating) Malfunction Decision Conditions During operation of cooling and heating, when compressor tank temperature data (103°C) is detected by the compressor tank temperature sensor. Malfunction Caused Faulty compressor tank temperature sensor 2/3 way valve closed ...
Page 142
17.4.26 F98 (Input Over Current Detection) Malfunction Decision Conditions During operation of cooling and heating, when an input over-current (X value in Total Running Current Control) is detected by checking the input current value being detected by current transformer (CT) with the compressor running.
Page 143
17.4.27 F99 (DC Peak Detection) Malfunction Decision Conditions During startup and operation of cooling and heating, when inverter DC peak data is received by the outdoor internal DC Peak sensing circuitry. Malfunction Caused DC current peak due to compressor failure. ...
High Voltage is generated in the electrical parts area by the capacitor. Ensure that the capacitor has discharged sufficiently before proceeding with repair work. Failure to heed this caution may result in electric shocks. 18.1 CS-RZ25TKR CS-RZ35TKR 18.1.1 Indoor Electronic Controllers, Cross Flow Fan and Indoor Fan Motor Removal Procedures 18.1.1.1...
Page 145
9 Detach connectors as labeled from the 8 Pull out the main electronic controller. Then pull out main electronic controller controller gently. halfway. AC303 5 Detach the Earth wire screw, lead wires AC306 (Black) and AC304 (Red) CN-FM from the terminal board. 7 Remove screw to remove terminal board complete.
Page 146
18.1.1.4 To Remove Control Board Figure 6 18.1.1.5 To Remove Cross Flow Fan and Indoor Fan Motor Figure 7 15 Remove the bearing by pulling it out gently. 14 Remove the 2 screw from the evaporator Figure 8...
WARNING High Voltage is generated in the electrical parts area by the capacitor. Ensure that the capacitor has discharged sufficiently before proceeding with repair work. Failure to heed this caution may result in electric shocks. 18.2 CS-RZ50TKR CS-RZ60TKR CS-RZ71TKR CS-RZ80TKR 18.2.1 Indoor Electronic Controllers, Cross Flow Fan and Indoor Fan Motor Removal Procedures...
Page 149
18.2.1.3 To Remove Electronic Controller Pull out the main Detach connectors as labeled from the electronic controller. electronic controller. Then pull out the main controller gently. AC303 Detach the Earth wire screw, lead wires AC306 CN-FM (Black) and AC304 (Red) from the terminal board.
Page 150
18.2.1.5 To Remove Control Board Figure 6 18.2.1.6 To Remove Cross Flow Fan and Indoor Fan Motor Figure 7 Holdfast Remove the screw from the evaporator. Remove the bearing by pulling it out gently. Figure 8...
18.3 Outdoor Electronic Controller Removal Procedure 18.3.1 CU-RZ25TKR CU-RZ35TKR Caution! When handling electronic controller, be careful of electrostatic discharge. Remove the 5 screws of the Top Panel. Remove the Control Board as follows: Screws Top Panel Release 3 Terminal Screws Connectors, L, N and Earth Wire Screw.
Page 153
18.3.2 CU-RZ50TKR CU-RZ60TKR Caution! When handling electronic controller, be careful of electrostatic discharge.
Page 154
18.3.3 CU-RZ71TKR Caution! When handling electronic controller, be careful of electrostatic discharge. Remove the 5 screws of the Top Panel. Remove 2 screws for the plate of Terminal Board Cover. Top Panel Screw Plate of Terminal Board Cover Screws Screws Screws Fig.
Page 155
18.3.4 CU-RZ80TKR Caution! When handling electronic controller, be careful of electrostatic discharge. Remove the 4 screws of the Top Panel. Remove the Control Board. Fig. 4 Remove the 8 screws of the Electronic Controller. Fig. 1 Remove the 10 screws of the Front Panel. Fig.
19. Technical Data Technical data provided are based on the air conditioner running under free frequency. 19.1 Sensible Capacity Chart 19.1.1 CS-RZ25TKR CU-RZ25TKR Cooling Indoor (°C) Outdoor (°C) 2729 2542 3072 2744 2864 2682 2682 2584 3160 2096 3384 2229...
20.3 Piping Length Correction Factor The characteristic of the unit has to be corrected in accordance with the piping length. 20.3.1 CS-RZ25TKR CU-RZ25TKR CS-RZ35TKR CU-RZ35TKR 1.020 Cooling Capacity 1.001 1.000 1.0000 0.980 0.9793 0.960 0.9107 0.9085 0.940 0.920 0.900 Piping Length (m) 1.010...
21. Exploded View and Replacement Parts List 21.1 Indoor Unit 21.1.1 CS-RZ25TKR CS-RZ35TKR CWH5 5025J CWH5 5051J Note The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
Page 178
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CS-RZ25TKR CS-RZ35TKR REMARK CHASSIS COMPLETE ACXD50C00440 ← FAN MOTOR L6CBYYYL0195 ← CROSS-FLOW FAN COMPLETE CWH02C1159 ← SCREW - CROSS-FLOW FAN CWH551146 ← BEARING ASSY CWH64K1006 ← EVAPORATOR ACXB30C00770 ACXB30C02470 FLARE NUT (LIQUID) CWT251048 ←...
Page 179
21.1.2 CS-RZ50TKR CS-RZ60TKR CS-RZ71TKR CS-RZ80TKR CWH 55025J CWH 55051J Note The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
Page 180
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CS-RZ50TKR CS-RZ60TKR REMARK CHASSIS COMPLETE ACXD50C01590 ← FAN MOTOR L6CBYYYL0193 ← CROSS-FLOW FAN COMPLETE CWH02C1136 ← BEARING ASSY CWH64K1010 ← SCREW - CROSS-FLOW FAN CWH551146 ← EVAPORATOR ACXB30C15820 ACXB30C11130 FLARE NUT (LIQUID) CWT251030 ←...
Page 181
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CS-RZ71TKR CS-RZ80TKR REMARK CHASSIS COMPLETE ACXD50C01590 ← FAN MOTOR L6CBYYYL0194 ← CROSS-FLOW FAN COMPLETE CWH02C1136 ← BEARING ASSY CWH64K1010 ← SCREW - CROSS-FLOW FAN CWH551146 ← EVAPORATOR ACXB30C10760 ← FLARE NUT (LIQUID) CWT251030 ←...
21.2 Outdoor Unit 21.2.1 CU-RZ25TKR CU-RZ35TKR Note: The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
Page 184
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CU-RZ25TKR CU-RZ35TKR REMARK OPERATING INSTRUCTION ACXF55-11360 ← INSTALLATION INSTRUCTION ACXF60-16830 ← (NOTE) All parts are supplied from PAPAMY, Malaysia (Vendor Code: 00029488). “O” marked parts are recommended to be kept in stock.
Page 185
21.2.2 CU-RZ50TKR Note: The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
Page 187
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CU-RZ50TKR REMARK INSTALLATION INSTRUCTION ACXF60-16830 FLEXIBLE PIPE (L-TUBE) CWH5850080 PACKING-L. TUBE CWB81012 (NOTE) All parts are supplied from PAPAMY, Malaysia (Vendor Code: 00029488). “O” marked parts are recommended to be kept in stock.
Page 188
21.2.3 CU-RZ60TKR Note: The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
Page 190
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CU-RZ60TKR REMARK INSTALLATION INSTRUCTION ACXF60-16830 FLEXIBLE PIPE (L-TUBE) CWH5850080 PACKING-L.TUBE CWB81012 (NOTE) All parts are supplied from PAPAMY, Malaysia (Vendor Code: 00029488). “O” marked parts are recommended to be kept in stock.
Page 191
21.2.4 CU-RZ71TKR Note: The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
Page 192
CONTROL BOARD COVER CO. ACXH13C00170 PLATE - C. B. COVER TERMINAL CWH131470 PACKING CWB81043 TUBE ASSY (CAP.TUBE) ACXT00C20450 RECEIVER CWB14030 ACCUMULATOR ACXB13-00010 PANASONIC BADGE CWE373439 INVERTER BADGE CWE373441 SOUND PROOF MATERIAL CWG302636 SOUND PROOF MATERIAL (COMP. TOP) CWG302246 DISCHARGE MUFFLER CWB121013...
Page 193
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CU-RZ71TKR REMARK STRAINER CWB111032 BAG-COMPLETE CWG87C900 FLEXIBLE PIPE (L-TUBE) CWH5850080 PACKING-L .TUBE CWB81012 OPERATING INSTRUCTION ACXF55-11380 INSTALLATION INSTRUCTION ACXF60-16830 (NOTE) All parts are supplied from PAPAMY, Malaysia (Vendor Code: 00029488). “O”...
Page 194
21.2.5 CU-RZ80TKR Note: The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service part.
Page 195
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CU-RZ80TKR REMARK CHASSIS COMPLETE CWD52K1190 ANTI - VIBRATION BUSHING CWH50055 PACKING CWB81043 COMPRESSOR 9KD240XBA21 NUT - COMPRESSOR MOUNT CWH561049 SOUND PROOF MATERIAL CWG302246 SOUND PROOF MATERIAL CWG302951 FAN MOTOR BRACKET CWD541127 FAN MOTOR EHDS80C60AC SCREW - FAN MOTOR BRACKET CWH551217...
Page 196
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CU-RZ80TKR REMARK PANASONIC BADGE CWE373439 INVERTER BADGE CWE373441 OPERATING INSTRUCTION ACXF55-11380 INSTALLATION INSTRUCTION ACXF60-16830 PLATE - C. B. COVER TERMINAL CWH131332 (NOTE) All parts are supplied from PAPAMY, Malaysia (Vendor Code: 00029488).