3300/25 Dual Accelerometer Input Monitor Operation Manual
13.3 Test the Danger Setpoint Level
1. Adjust the function generator amplitude past the
Danger setpoint level and verify that the DANGER
LED comes on (flashing if the First Out option is
selected).
2. Verify that the Danger Relay changed state.
NOTE: The Danger Relay will not change state if:
• Danger Bypass is on
• Danger AND voting logic is selected and only
one channel exceeds its setpoint.
AND voting is not active if either channel is
bypassed or not OK.
3. Press the RESET switch on the System Monitor.
4. Verify that the ALERT and DANGER LEDs remain
on and steady.
32