Siemens SITRANS RD500 Manual page 10

Configuring sitrans rd500 for connection to multiranger with modbus rtu
Hide thumbs Also See for SITRANS RD500:
Table of Contents

Advertisement

Planning/configuring
3.3 Configuring RD500 to Read MODBUS Registers from MultiRanger
9. Repeat steps 5 to 8 to add more registers for monitoring in SITRANS RD500.
Note
The MODBUS register map is available in the MultiRanger 100/200 instruction manual
(https://support.industry.siemens.com/cs/us/en/view/19163413). The table below has
some commonly used registers.
10. Click on Overview and then Alarms. Enter alarm values for the monitored registers and
click on Apply.
10
Description
Primary Variable
Transducer Temperature
mA Output
Pump Starts
Pump Hours
Discrete Inputs
Register
Type
Access
401010
Word
Read Only
401030
Word
Read Only
401110
Word
Read/Write
401470
Word
Read Only
401450
Long
Read Only
401070
Bit
Read Only
Configuring SITRANS RD500 for connection to MultiRanger with MODBUS RTU
Sign
Before DP After DP
Soft sign
5
Soft sign
3
Unsigned
2
Unsigned
8
Unsigned
8
Unsigned
-
Application examples, 09/2020, AG111710
2
0
2
0
0
-