¢ Dimensions
¢ Specifications
Power supply
Power source frequency
Input power
Temperature
Humidity
Dimensions (H × W × D)
Weight
Fuse capacity
Wiring specifications
Use
Power supply cable
Transmission cable
Modbus cable
Transmission specifications
Transfer mode
Communication method
Communication speed
Synchronous system
Data bit
Parity
Stop bit
Network
Maximum cable length
3-4. Modbus convertor for VRF (UTY-VMGX)
3/16 × 13/16 = 3-1/8
(4 × 20 = 80)
Hole pitch
5-Ø1/2 (13)
For dust proof bushing
9-1/2 (241)
4-Ø3/16 (5)
For M4 × 16 mm screws
Operating
Packaged
Packaged
Cable size
20 to 16 AWG
60245 IEC 57 or equivalent
2
(0.5 to 1.25 mm
)
22 AWG
Non-polar 2 core, twisted pair
2
(0.33 mm
)
26 to 16 AWG
2
3 Wire + Sheathed PVC cable
(0.128 to 1.25 mm
)
3/8 (10)
2-11/16 (69)
Ø7/8 (22)
For conduit
2-Ø3/16 (5)
For M4 × 16 mm
screws
8-7/8 (225)
2-1/8 (54)
Hole pitch
10-1/4 (260)
V
Hz
W
°C
°C
%
mm
2-1/8 × 10-1/4 × 5-7/8 (54 × 260 × 150)
lb (g)
A
Wire type
LEVEL 4 (NEMA)
solid core shielded
AWG 16—26
Half-duplex operation, Master/Slave method
bps
Asynchronous communication method
bit
bit
ft (m)
- (05-134) -
Unit: in (mm)
1 Ø AC 208—240
50/60
2.0
32 to 114.8 (0 to 46)
14 to 140 (-10 to 60)
0 to 95 (RH)
No condensation
2 (1,100)
2
Remarks
1 Ø AC 208—240 V 50/60 Hz,
2 wire + ground (Always ground
the unit)
®
LonWorks
compatible cable
RTU mode
9,600/19,200
8
even/odd/none
2 (no parity)/1
3 wire RS485
3,280 (1,000)
3. Adaptor/Convertor units