Section 4
IEC 60870-5-103
<9> DOUBLE-POINT INFORMATION
WITH TRANSIENT AND ERROR
0
0
Time stamp (CP56Time2a)
4.5.5

Display of busbar differential currents

The differential currents are displayed for each corresponding busbar zone (1..32) (see transfer
of differential currents).
Table 28: Used attributes of ASDU 10 for differential current
COT
1 Spontaneous
The group number 75 (0x4B) is used to display busbar differential currents and is therefore
only assigned to the Central Unit (CAA = 0).
Table 29: Directory entry for GIN 0x4B00 (header)
COD
<10> Description
<1> Current value
The number of valid entries corresponds to the number of bus-bar zones and thus limited to
the range [1...32].
Each of the entries 1...32 in the group relates to a given busbar zone.
22
46 H
01 H
Current value <1>
DATA STRUCTURE <23>
14
1,0
1
1,0
0
0
0
0
<0 .. 3>
BINARY TIME
<14>
7
1,0
CAA
0 REB500 CU
Data type
<1> os8ascii
<3> UI
© 2019 - 2020 Hitachi Power Grids. All rights reserved
Generic identification
number
Kind of description
DATA TYPE
DATA SIZE
NUMBER, CONT
DATA TYPE
DATA SIZE
NUMBER, CONT
DATA TYPE
DATA SIZE
NUMBER, CONT
Length
Number
Value / Significance
21
1
Differential currents
1
1
Number of valid entries
Communication protocol manual IEC 60870-5-103
1MRK 511 451-UEN Rev. C
Group <46H .. 49H>
Entry <1 .. 255>
KOD
GDD
GDD 1
GID 1
GDD 2
GID 2
GUID-A271FDFD-8D47-4A1F-B45E-51DB2BD31164 v2
FUN
254 Generic
Distributed busbar protection REB500