Siemens Sinamics S120 Manual page 109

Power units, booksize c/d type format
Hide thumbs Also See for Sinamics S120:
Table of Contents

Advertisement

Figure 6-4
Power Units in Booksize C/D-Type Format
Manual, 01/2017, 6SL3097-4AC20-0BP1
The protective conductor must be dimensioned in accordance with the local installation rules
for equipment with increased leakage currents. As a minimum, one of the following conditions
must be satisfied:
The protective conductor is routed so that along its complete length it is protected against
mechanical damage.
The protective conductor has a cross-section ≥ 10 mm
A second protective conductor with the same cross-section is provided.
When establishing the connection using an industrial plug connector according to EN
60309, the protective conductor of a multi-conductor cable must have a cross-section
≥ 2.5 mm
Cu.
2
As a conductor of a multi-conductor cable, the protective conductor has a cross-section ≥
2.5 mm
Cu.
2
The cable cross-section must be dimensioned in compliance with local installation rules.
The cable cross-sections must be dimensioned in compliance with local installation rules.
Additional details are provided in the following document "Dimensioning the protective conduc-
tor for SINAMICS S120 Booksize
(https://support.industry.siemens.com/cs/ww/en/view/109738572)".
Same cross-section as the line conductor of the motor cable.
Protective connection concept, SINAMICS S120 booksize
6.9 Protective connection and equipotential bonding
Cu.
2
Cabinet design
109

Advertisement

Table of Contents
loading

Table of Contents