Write Locking; Master Reset - Siemens SITRANS Probe LU Quick Start Manual

Radar transmitters
Hide thumbs Also See for SITRANS Probe LU:
Table of Contents

Advertisement

Security
Local operation enable
Local Operation can be enabled or disabled via PDM. Go to Identification > Device > Local
Operation Enable and select the desired setting.

Write Locking

Write locking prevents any changes to parameters via PDM or via the handheld programmer,
but still allows access to the device.
Via PDM, open the menu Device – Write Locking, and select Off or On.
Hand programmer values
Via the handheld programmer:
• Open Identification Menu, then scroll down to CONFIG.
• Press Right ARROW
1. Identification
1.3. Configuration
1.3.5. Lock
• To enable programming, set LOCK to 2457. To disable programming, enter any other value.
Remote operation enable
Remote Operation can be enabled or disabled via the handheld programmer.
0
Off
Values
1
On
• Open Identification Menu, then scroll down to CONFIG.
• Press Right ARROW
1. Identification
1.2. Configuration
1.2.2. Remote Lockout
• To enable programming, set REMLOCK to 0. To disable programming, enter 1.

Master Reset

In PDM, open the menu Device – Master Reset, to access the reset options, including Factory
Reset.
Page EN-12 SITRANS Probe LU (PROFIBUS PA) – QUICK START MANUAL
2457 (unlock value)
any other value
to open the Config Menu, then scroll down to LOCK.
Remote operation enabled.
Remote operation disabled.
to open the Config Menu, then scroll down to REMLOCK.
Off
Enables parameter changes
On
Disables parameter changes
A5E32081626

Advertisement

Table of Contents
loading

This manual is also suitable for:

7ml1234-78910-abc-d

Table of Contents