13.3

Technical specifications for POM

product brand name
Product designation
General technical data:
Type of load
Equipment marking / acc. to DIN EN 81346-2
Supply voltage:
Type of voltage / of the supply voltage
Supply voltage / at AC / rated value
Relative negative tolerance / of the supply volt-
age
Relative positive tolerance / of the supply volt-
age
Supply voltage frequency / 1 / rated value
Supply voltage frequency / 2 / rated value
Relative symmetrical tolerance / of the supply
voltage frequency
Power capacity
of the module / with star connection / at 40
°C / with fan / maximum
of the module / with star connection / at 40
°C / without fan / maximum
maximum permissible
Switching capacity current / per phase / maxi-
mum
Design of the electrical isolation
Recovery time / after power failure / typical
Type of electrical connection / for supply voltage Connector, 3-pin with tension
Type of connectable conductor cross-section
for supply voltage / solid
for supply voltage / finely stranded / with core
end processing
for AWG conductors / for supply voltage
SIPLUS HCS4200
Operating Instructions, 11/2015, A5E35066204A/RS-AA/002
SIPLUS
POM4220 Lowend
Ohmic load
Q
AC
230 V
10 %
10 %
50 Hz
60 Hz
5 %
16.1 kW
7.3 kW
16.1 kW
35 A
Optocoupler and/or protective impedance between main circuit and
PELV
1 s
spring connection
1x (0.2 ... 10 mm²)
1x (0,25 ... 6 mm²)
1x(24...8)
Technical specifications
13.3 Technical specifications for POM
POM4220 Midrange
277 V
25 %
8 %
27.7 kW
9 kW
27.7 kW
50 A
Connector, 3-pin
1x (0,75 ... 16 mm²)
1x (0,75 ... 16 mm²)
1x (18 ... 4)