Technical data
Power supply
Operating voltage
Frequency
Power consumption
Radio parameters
Frequency band
Maximum radio-frequency power
Thread standard
Thread channel
Switching capacity of relays
Voltage
Current
No internal fuse.
External preliminary protection with max. C 16 A circuit breaker in the supply lines
required under all circumstances.
External protection for incoming cable
Circuit breaker
Circuit breaker tripping characteristic
Contact life at AC 230 V
At 8 A res.
Insulation strength
Between relay contacts and coil
Between relay contacts (same pole)
Electrical connections
Connection terminals
For solid wires
For stranded wires
Ambient conditions and protection classification
Safety class as per EN60730
Degree of protection of housing as per EN
60529
Classification as per EN 60730
Function of automatic control devices
Operation altitude
Degree of contamination
Overvoltage category
Smart Infrastructure
WARNING
AC 230 V (+10/-15%)
48...63 Hz
5 VA
2.4...2.4835 GHz
15 dBm
IEEE 802.15.4
11-26
AC 24...230 V
Q11- Q12 Max. 5 A
Q11- Q14 Max. 8 (2) A
Q21- Q22 Max. 5 A
Q21- Q24 Max. 8 (2) A
Max. 16 A
Type B, C or D to EN 60898 and EN 60947
Guided value:
1 x 10
cycles
5
AC 5,000 V
AC 1,000 V
Screw terminals
2 x 1.5 mm
2
1 x 2.5 mm
(Min. 0.5 mm
)
2
2
Class II
IP30
Type 1
< 3000 m
2
III
7
A6V11562464_en--_a
2019-09-19

Advertisement