Mitsubishi Electric MELSEC Q Series Reference Manual page 574

Cc-link ie controller network
Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

No.
Name
Online switch
SB0043
(own station)
Station setting
SB0044
(own station)
Baton pass status
SB0047
(own station)
Control station status
SB0048
(own station)
Data link status of own
SB0049
station
Own station's CPU
SB004A
status (1)
Own station's CPU
SB004B
status (2)
Cyclic transmission
SB004C
start accept status
(own station)
572
Stores the mode of own station. (
OFF: Online
ON: Other than online
Stores the network type that is set by parameters of own station.
OFF: Normal station
ON: Control station
Stores the baton pass status (transient transmission availability) of the own
station.
OFF: Normal
ON: Error
When an error is identified, the cause of the error can be checked in Baton
pass status (own station) (SW0047) and Cause of baton pass interruption
(SW0048).
Depending on the link refresh timing, Baton pass status (own station)
(SW0047) or Cause of baton pass Interruption (SW0048) and the update
may be offset by one sequence scan.
Stores network type (current status) of own station.
OFF: Normal station
ON: Control station (when SB0044 is turned ON)
Sub-control station (when SB0044 is turned OFF)
(Condition)
• Valid when Baton pass status (own station) (SB0047) is OFF.
When Baton pass status (own station) (SB0047) is turned ON (error), data
prior to error is held.
Stores the data link status of own station.
OFF: Normal
ON: Error
When an error is identified, the cause of the error can be checked in Cause
of data link stop (SW0049).
Depending on the link refresh timing, Cause of data link stop (SW0049) and
the update may be offset by one sequence scan.
Stores the continuation error status of the CPU module of the own station.
OFF: Normal
ON: Continuation error
Stores the stop error status of the CPU module of the own station.
OFF: Normal
ON: Stop error
Turned ON when startup request for cyclic transmission due to Link startup
(own station) (SB0000) is received.
OFF: Not received (SB0000 is OFF)
ON: Startup received (SB0000 is ON)
(Condition)
• Valid when Baton pass status (own station) (SB0047) is OFF.
When Baton pass status (own station) (SB0047) is turned ON (error), data
prior to error is held.
Description
Page 182, Section 6.2 (7))
Availability
Control
Normal
station
station