Appendix C – Installation Planning Guide
Installation Planning Guide for 15-100kVA UPS
UPS kVA/ kW
Rating
15 kVA/ 13.5 kW
20 kVA/ 22.5 kW
25 kVA/ 22.5 kW
30 kVA/ 27 kW
50 kVA/ 45 kW
80 kVA/ 72 kW
100 kVA/ 90 kW
Power Demand at 100% Load
kVA
PF
15
>0.99
20
>0.99
25
>0.99
30
>0.99
50
>0.99
80
>0.99
100
>0.99
Power Demand at 100% Load
kVA
PF
15
0.9
20
0.9
25
0.9
30
0.9
50
0.9
80
0.9
100
0.9
Battery Capacity Required
for Full Load Output
kVA
15
20
25
30
50
80
100
1 – External overcurrent overprotection not needed if battery cabinet(s) are each equipped with an appropriate internal circuit breaker
2 – External feeder cables may change depending on number of battery cabinets placed in parallel.
3 – Feeder ampacity based on worst case temperature conditions and sized to be protected by overcurrent device.
118
Rev. 1.6
TOSHIBA
Standard System: 208/120V Input, 208/120V Output
General Mechanical Information
Dimensions
(W x D x H)
Inches
20.12 x 37.4 x 65.06
20.12 x 37.4 x 65.06
20.12 x 37.4 x 65.06
20.12 x 37.4 x 65.06
32.1 x 37.2 x 73.8
32.1 x 37.2 x 73.6
32.1 x 37.2 x 73.6
Primary AC Input (208/120V 3-Phase / 4-Wire)
Suggested External
Feeder Breaker
Amps
Amps
42 (57)
90 A
56 (71)
125 A
70 (85)
150 A
84 (99)
175 A
140 (154)
250 A
224 (239)
400 A
280 (295)
500 A
Bypass AC Input (208/120V 3-Phase / 4-Wire)
Suggested External
Feeder Breaker
Amps
Amps
42
70 A
56
90 A
69
110 A
83
150 A
139
225 A
222
350 A
278
450 A
Battery Backup (288VDC Nominal)
Maximum Discharge
at Full Load Output
kWB
Amps DC
14.7
64 A
19.6
85 A
24.5
107 A
29.4
128 A
49.5
215 A
79.2
344 A
98.9
430 A
4400 UPS
Weight
Approximate Full-
Bare (w/ Int Batt.)
Load Heat Loss
Lbs.
kBtu/Hr
725 (1015)
4.6
730 (1020)
6.1
750 (1035)
7.6
760 (1045)
9.1
965 (1920)
15.2
1550 (N/A)
24.3
1650 (N/A)
30.4
Suggested Minimum Feeder Wire Size
Per Phase / Neutral
AWG or kcmil at 75º C Temp. Rating
(1) x 4 AWG / (1) x 2 AWG
(1) x 2 AWG / (1) x 2 AWG
(1) x 2 AWG / (1) x 2 AWG
(1) x 2 AWG / (1) x 2 AWG
(1) x 4/0 AWG / (1) 250 kcmil
(2) x 2/0 AWG – (1) x 500 kcmil /
(2) x 350 kcmil
(2) x 4/0 AWG – (1) x 600 kcmil /
(2) x 500 kcmil
Suggested Minimum Feeder Wire Size
Per Phase / Neutral
AWG or kcmil at 75º C Temp. Rating
(1) x 6 AWG / (1) x 2 AWG
(1) x 3 AWG / (1) x 2 AWG
(1) x 2 AWG / (1) x 2 AWG
(1) x 2 AWG / (1) x 2 AWG
(1) x 4/0 / (1) 250 kcmil
(2) x 2/0 AWG – (1) x 400 kcmil /
(2) x 300 kcmil
(2) x 3/0 AWG – (1) x 600 kcmil /
(2) x 500 kcmil
Suggested External
Suggested Minimum Feeder
Feeder Breaker
1
Wire Size Per Polarity
Amps
AWG or kcmil at 75º C Temp. Rating
100 A
150 A
175 A
200 A
350 A
600 A
700 A
4400 Series Installation and Operation Manual – 64527-008
Page 1 of 3
Mechanical Clearance for Ventilation
and Maintenance Access
Top:
Front:
16 in
36 in
(406 mm)
(900 mm)
Suggested Maximum Feeder Length
For Min. Wire Size in Steel Conduit
Feet
380
380
380
380
380
380
380
Suggested Maximum Feeder Length
For Min. Wire Size in Steel Conduit
Feet
380
380
380
380
380
380
380
Suggested Maximum
Feeder Length For Min. Wire
Size in Steel Conduit
(1) x 2 AWG
(1) x 2 AWG
(1) x 2 AWG
(1) x 2 AWG
(1) x 250 kcmil
(2) x 250 kcmil
(2) x 350 kcmil
4400-IPG-208/120v-208/120V
Bottom/
Sides/
Back:
0 in.
(0 mm)
Feet
70
70
70
70
70
70
70