Advertisement

ABB i-bus
®
KNX
Commissioning
3.4.1

Settings in ETS 5

An additional Properties window is available in ETS for setting the additional physical addresses.
After insertion of the Router into the line, the ETS automatically reserves the first five free addresses of
this line for the tunneling servers of the Router. This is a property of the ETS and cannot be changed.
The addresses will be available in the device after the first download.
If this is not desired, the setting can be changed manually in the Properties window.
To change the address, mark the current device address or additional address and then select the desired
numerals using the up or down arrow key. The changed address is saved when another address is
marked.
The changed addresses are adopted by the device only after a download.
Park
If the option Park is activated for a tunnel, this tunnel will receive the address 15.15.255.
If the option Park is selected for all tunneling servers, all tunneling servers will be assigned the address
15.15.255. Only one tunneling server is available as a result.
32 2CDC502099D0211 Rev. A | IPR/S 3.5.1