Measuring Inputs; Current Measurement - Siemens SENTRON 7KT PAC1600 Equipment Manual

Energy meter
Hide thumbs Also See for SENTRON 7KT PAC1600:
Table of Contents

Advertisement

MID-approved
MID-approved devices are included in the portfolio. These devices are suitable for billing
purposes. Certain actions cannot be performed on devices with an MID mark, e.g. firmware
update, reset of energy values.
3.2

Measuring inputs

3.2.1

Current measurement

NOTICE
Device damage due to DC current
The device is not suitable for measuring DC current.
Only measure AC current with the device.
Design of the 5 A device
The 5 A device is designed for a rated current of 5 A for connecting standard current
transformers.
Each current measuring input can take a continuous load of 6 A.
Design of 63 A and 80 A devices
The 63 A and 80 A devices are designed to be connected directly to the low-voltage grid.
7KT16 energy meter
Equipment Manual, 09/2020, 2514284147-04
Description
3.2 Measuring inputs
17