Appendix 7
This chapter describes when the temperature control module is mounted on an extension base unit in a redundant system
with redundant extension base unit.
Restricted functions and specifications
This section describes the restricted functions and specifications of when the temperature control module is mounted on an
extension base unit in a redundant system with redundant extension base unit.
Function
Function
Self-tuning function
Simultaneous temperature rise
function
Inter-module peak current
suppression function
Inter-module simultaneous
temperature rise function
Interrupt Function
I/O Signal
I/O Signal
Setting/operation mode command
(Y1)
PID control forced stop command
(YC to YF)
Module FBs
Name
M+R60TC_StartPeakCurrentSuppres
sionBetweenModule
M+R60TCBW_StartPeakCurrentSup
pressionBetweenModule
M+R60TC_StartSimultaneousTemper
atureRiseBetweenModule
M+R60TCBW_StartSimultaneousTe
mperatureRiseBetweenModule
Using the Module in the Redundant
System with Redundant Extension Base
Unit
Restriction
If the system is switched during transition from setting mode to operation mode, starting ST may not start.
To start the starting ST properly, set "PID continuation flag" to "1: Continue."
If the system is switched during execution of the simultaneous temperature rise AT(auto tuning), the auto tuning may
stop.
To start the simultaneous temperature rise AT properly, set "PID continuation flag" to "1: Continue."
This function cannot be used.
When this function is used, a peak current suppression function master not exist error between multiple module (error
code: 1AE1H) occurs.
This function cannot be used.
When this function is used, a simultaneous temperature rise function master not exist error between multiple module
(error code: 1AF1H) occurs.
The interrupt program cannot be executed.
Restriction
If the system is switched during the mode shift processing, temperature control may become unstable.
To stabilize the temperature control, set "PID continuation flag" to "1: Continue."
When the system is switched, it may take time to stop the PID control.
Configure an external circuit to stop the PID control as necessary.
Restriction
Cannot be used.
When the FB is used, proper operation cannot be guaranteed.
Appendix 7 Using the Module in the Redundant System with Redundant Extension Base Unit
A
APPX
349