Wiring Connection - Toshiba BMS-TP0640ACE Manual

Touch screen controller, tcs-net air conditioning control system
Table of Contents

Advertisement

Wiring Connection

The following describes wiring connections of the Energy Monitoring Relay Interface when it is used in
the air conditioner control system.
• Terminator resistor setting
Set the RS-485 terminator resistor by the TCS-NET Relay Interface.
Do not set it by the Energy Monitoring Relay Interface.
• Shield earthing
The shield earth of the RS-485 signal wires should be single-point earth. Earth the wires on the
Intelligent server side.
Other shield lines should be closed, and the terminal end should be open and insulated.
• Connection of power meter
Use a power meter with a pulse generator.
Connect the non-voltage contact output of the power meter to the Energy Monitoring Relay Interface.
An external input circuit is shown below.
Input signal is electrically isolated by photo-coupler.
12V
Energy Monitoring Relay Interface
Power meter
(with pulse generator)
Input
terminal
DI-1 to DI-8
Contact
47