Note 7: Resistor braking of the drive
When the drive is in braking mode for a large part of its operation time, the
intermediate circuit DC voltage of the drive increases, the effect being similar to
increasing the supply voltage by up to 20 percent. The voltage increase should be
taken into consideration when determining the motor insulation requirement.
Example: Motor insulation requirement for a 400 V application must be selected as if
the drive were supplied with 480 V.
Note 8: Calculating the rise time and the peak line-to-line voltage
The peak line-to-line voltage at the motor terminals generated by the drive as well as
the voltage rise time depend on the cable length. The requirements for the motor
insulation system given in the table are "worst case" requirements covering
installations with 30 metre and longer cables. The rise time can be calculated as
follows: t = 0.8 · Û
the values of the graph by the supply voltage (U
supply unit or resistor braking, the Û
higher.
3.0
2.5
2.0
1.5
1.0
0.5
0.0
100
Note 9: Sine filters protect the motor insulation system. Therefore, du/dt filter can be
replaced with a sine filter. The peak phase-to-phase voltage with the sine filter is
approximately 1.5 × U
Note 10: Common mode filter is available as a separate option.

Permanent magnet motor

Only one permanent magnet motor can be connected to the inverter output.
It is recommended to install a safety switch between the permanent magnet motor
and the drive output. The switch is needed to isolate the motor during any
maintenance work on the drive.
/(du/dt). Read Û
LL
Û
/U
LL
N
du/dt
------------ - (1/s)
U
N
200
300
Cable length (m)
With du/dt Filter
.
N
and du/dt from the diagrams below. Multiply
LL
). In case of drives with an IGBT
N
and du/dt values are approximately 20 %
LL
5.5
5.0
du/dt
------------ - (1/s)
U
4.5
N
4.0
3.5
3.0
2.5
2.0
1.5
1.0
100
Without du/dt Filter
Planning the electrical installation
43
Û
/U
LL
N
200
300
Cable length (m)