FusionModule2000 Smart Modular Data Center
Product Description (380 V)

3.3.4.2 Operating Environment Specifications

Operating Environment
Table 3-39 describes the operating environment specifications of the NetCol5000-A in-row
precision air conditioner.
Table 3-39 Operating environment specifications
Item
Temperature range
Humidity range
Storage temperature
Storage humidity
Altitude
Protection level
Table 3-40 Derating coefficients
Altitude
Density
coefficient
Air
volume
coefficient
Cooling
capacity
coefficient
Note: The sensible heat ratio is always 100%.
Installation Requirements
Table 3-41 describes the NetCol5000-A installation requirements.
Issue 04 (2017-06-30)
1/2 inch BSPP: large diameter 20.955 mm; medium diameter 19.793 mm; small diameter 18.631 mm;
medium diameter tolerance 0–0.142 mm; small diameter tolerance 0–0.541 mm.
Specifications
18–45° C
20%–80% RH
-40° C to +70° C
5%–95% RH (non-condensing)
0–1000 m (derated when the altitude exceeds 1000 m. For the
derating coefficients, see Table 3-40.)
0
1000
1
0.887
1
0.887
1
0.940
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Indoor unit: IP20
Outdoor unit: IPX5
1500
2000
2500
0.835
0.785
0.737
0.835
0.785
0.737
0.909
0.878
0.846
3 System Architecture
3000
3500
4000
0.692
0.649
0.608
0.692
0.649
0.608
0.815
0.784
0.753