Cable Cross-Sections And End Sleeves - Siemens SINAMICS S120 Manual

Power units in booksize c/d-type format
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

U2, V2, W2, pro-
tective conductor,
BR+, BR-
4.1.2.1

Cable cross-sections and end sleeves

To assemble the motor cable, refer to the tables below for the connectable cable cross-
sections, the possible end sleeves and the terminal openings for the individual motor
connector variants.
Table 4- 1
When crimped, conductor end sleeves must not exceed the maximum dimensions of 2.9 x 5.0 mm
1)
(0.11 x 0.20 in), as otherwise individual conductors will not be able to be inserted or removed.
Power Units in Booksize C/D-Type Format
Manual, 12/2018, 6SL3097-5AC20-0BP0
BR- (white)
Motor protective conductor connection (PE)
U2, V2, W2
Locking lever (for push-in connector only)
Conductor cross-section
for cables with conductor
end sleeves
Screwdriver
Tightening torque
Connector with push-in terminal
1.5 mm
2
AWG 16
AWG 14
Motor connection, shield support and fabrication
4.1 Motor plug connector for Motor Modules 3 A ... 30 A
Spring-loaded terminal
(push-in)
1.5 ... 6 mm
AWG 16 ... AWG 10
-
-
2.5 mm
4 mm
2
2
AWG 12
Screw terminal
1.5 ... 6 mm
2
AWG 16 ... AWG 10
Slotted 0.8 x 4.0 mm
0.5 ... 0.6 Nm
4.4 lbf in
6 mm
Dimensions of the terminal
2
AWG 10
openings
1)
1)
2
75